Air concept (WELL v2, Q2 2025)
Intent
The WELL Air concept aims to achieve high levels of indoor air quality across a building’s lifetime through a range of strategies that include source elimination or reduction, active and passive building design and operation strategies and human behavior interventions.
Background
The WELL Air concept aims to ensure high levels of indoor air quality across a building’s lifetime through a range of strategies that include source elimination or reduction, active and passive building design and operation strategies and human behavior interventions.
People spend approximately 90% of their time in enclosed spaces1 – in homes, offices, schools or other building environments. During this time, inhalation exposure to indoor air pollutants can lead to a variety of negative short- and long-term health and well-being outcomes that can vary in severity. Less severe symptoms of exposure can include headaches, dry throat, eye irritation or runny nose, while more severe health outcomes can include asthma attacks, infection with Legionella bacteria and carbon monoxide poisoning.2–4 In the U.S. alone, indoor pollution contributes to thousands of cancer deaths and hundreds of thousands of respiratory health issues annually.5 In addition to public health concerns, estimates by the U.S. EPA suggest that net avoidable costs associated with indoor air pollution amount to well over $100 billion annually with 45% of those costs attributable to avoidable deaths from radon and environmental tobacco smoke, about 45% from lost productivity and about 10% from avoidable respiratory diseases.5
The most common indoor air contaminants are combustion sources, such as candles, tobacco products, stoves, furnaces and fireplaces, that release pollutants, such as carbon monoxide, nitrogen dioxide and small particles into the air.6 Building materials, furnishings, fabrics, cleaning products, personal care products and air fresheners can also all emit volatile organic compounds (VOCs) or semi-volatile organic compounds (SVOCs) into the indoor environment.7,8
Achieving the goal of clean indoor air requires both professionals and building users to engage not just in the conversation but also in the implementation of adequate approaches. Although indoor air quality can be managed primarily through eliminating the sources of air pollution and through adequate design solutions and human behavior modification5,9,10, some WELL features require installation of a specific treatment method or technology.
It is evident that the impact of improving indoor air quality is substantial11. In a recent global burden of disease study, household air pollution was rated as the tenth most important cause of ill health for the world’s population.12 Furthermore, The World Health Organization estimated that, globally, air pollution contributed to approximately seven million premature deaths in 2012.13 Around 600,000 of those were children under 5 years old.14 The WELL Air Concept seeks to implement holistic design strategies to promote clean air and minimize human exposure to harmful contaminants, in order to maximize benefits to productivity, well-being and health.
Features in the Air concept (WELL v2, Q2 2025)
- A01 Air Quality — Precondition
- A02 Smoke-Free Environment — Precondition
- A03 Ventilation Design — Precondition
- A04 Construction Pollution Management — Precondition
- A05 Enhanced Air Quality — Optimization
- A06 Enhanced Ventilation Design — Optimization
- A07 Operable Windows — Optimization
- A08 Air Quality Monitoring and Awareness — Optimization
- A09 Pollution Infiltration Management — Optimization
- A10 Combustion Minimization — Optimization
- A11 Source Separation — Optimization
- A12 Air Filtration — Optimization
- A13 Enhanced Supply Air — Optimization
- A14 Microbe and Mold Control — Optimization
Note
Read more about the evidence behind the WELL Air Concept. Note: Material from the research digests is not covered on the WELL AP exam.
Testing location
- Testing should be conducted under regular project conditions. For example, for naturally ventilated spaces, the windows should be open during testing.
- The WELL Performance Testing Agent should note whether the HVAC system (or any ventilation or air treatment method) is on or off during the data collection period.
- Sampling points must be representative of typical occupiable areas within the sampling zone and located where occupants would typically be situated (e.g., at workstations).
- Sampling points must be at the following heights above the finished floor:
- 1.1-1.7 m [3.6-5.6 ft] at locations where occupants would typically be seated or standing.
- Sampling points must be at least 1 m [3.3 ft] away from walls, doors, windows, air supply/exhaust outlets and any occupants that are present during testing. To the extent possible, sampling points should be at least 5 m [16.4 ft] from exterior doors.
- For projects with multiple floors, measurements must be distributed across different floors, including the lowest and highest regularly occupied floor (excluding floors with only leased space in WELL Core and Core & Shell).
- Where sampling points for A01 and A05 are the same, tests used for A01 can be analyzed to determine whether results meet A05 requirements (i.e., separate tests are not required for A05 if all necessary parameters are available from samples taken for A01).
Sampling quantity
Number of Sampling Points Required Based on Project Area and Number of Floors
|
Floors |
Total Project Area* |
|
|
<50,000 ft2 |
≥50,000 ft2 |
|
|
<4,600 m2 |
≥4,600 m2 |
|
|
1 |
2 |
3 |
|
2 |
2 |
4 |
|
3-4 |
3 |
5 |
|
5-7 |
3 |
6 |
|
8-10 |
4 |
7 |
|
11-15 |
5 |
8 |
|
16-20 |
6 |
9 |
|
>20 |
7 |
10 |
*For WELL Core projects, to determine the number of sampling points:
- For Feature A01 (preconditions), use the project’s total non-leased area for the purpose of project area in this table. Testing in the leased area is not required unless the non-leased area does not make up the minimum required testable area.
- For Feature A05 (optimization), use the project’s total area. In addition to testing in non-leased areas, the WELL Performance Testing Agent must have access to test within tenant spaces (either before or after fit-out), representing at least 10% of the leased area.
- For Multifamily Residential projects, unless otherwise stated, sample points should be taken as follows:
- Projects with 10 dwelling units or fewer: two of each unit type
- Projects with more than 10 dwelling units: 5% of each unit type, with a minimum of three and a maximum of 40 units of each unit type
- To determine the test quantity for all other non-dwelling spaces, follow Table 2 sampling point guidance for the total area of regularly occupied spaces only, not the total project area (e.g., occupied lobbies and gyms are considered regularly occupied spaces and therefore would be included in the Table 2 calculations; common areas such as hallways are not considered regularly occupied spaces and therefore would not be included in the calculations).
References
- Klepeis NE, Nelson WC, Ott WR, et al. The National Human Activity Pattern Survey (NHAPS): A resource for assessing exposure to environmental pollutants. J Expo Anal Environ Epidemiol. 2001;11(3):231-252. doi:10.1038/sj.jea.7500165
- Joshi S. The sick building syndrome. Indian J Occup Environ Med. 2008;12(2):61. doi:10.4103/0019-5278.43262
- Selgrade MK, Plopper CG, Gilmour MI, Conolly RB, Foos BSP. Assessing the health effects and risks associated with children’s inhalation exposures - Asthma and allergy. J Toxicol Environ Heal - Part A Curr Issues. 2008;71(3):196-207. doi:10.1080/15287390701597897
- U.S. Environmental Protection Agency. Indoor Air Pollution: An Introduction for Health Professionals. https://www.epa.gov/indoor-air-quality-iaq/indoor-air-pollution-introduction-health-professionals.
- Jacobs DE, Kelly T, Sobolewski J. Linking public health, housing, and indoor environmental policy: Successes and challenges at local and federal agencies in the United States. Environ Health Perspect. 2007;115(6):976-982. doi:10.1289/ehp.8990
- Cooperative Extension Service, University of Kentucky. Common Indoor Air Pollutants: Sources And Health Impacts. 2000. http://www2.ca.uky.edu/hes/fcs/factshts/HF-LRA.161.PDF.
- U.S. Environmental Protection Agency. Volatile Organic Compounds’ Impact on Indoor Air Quality. https://www.epa.gov/indoor-air-quality-iaq/volatile-organic-compounds-impact-indoor-air-quality.
- Wallace LA, Pellizzari E, Leaderer B, Zelon H, Sheldon L. Emissions of volatile organic compounds from building materials and consumer products. Atmos Environ. 1987;21(2):385-393. doi:10.1016/0004-6981(87)90017-5
- Takaro TK, Krieger J, Song L, Sharify D, Beaudet N. The Breathe-Easy home: The impact of asthma-friendly home construction on clinical outcomes and trigger exposure. Am J Public Health. 2011;101(1):55-62. doi:10.2105/AJPH.2010.300008
- Krieger J, Jacobs DE, Ashley PJ, et al. Housing interventions and control of asthma-related indoor biologic agents: a review of the evidence. J Public Health Manag Pract. 2010;16(5 Suppl):S11-S20. doi:10.1097/phh.0b013e3181fce56a
- Health Effects Institute. A Special Report on Global Exposure To Air Pollution and Its Disease Burden.; 2017. https://ccacoalition.org/en/resources/state-global-air-2017-special-report-global-exposure-air-pollution-and-its-disease-burden.
- Gakidou E, Afshin A, Abajobir AA, et al. Global, regional, and national comparative risk assessment of 84 behavioural, environmental and occupational, and metabolic risks or clusters of risks, 1990-2016: A systematic analysis for the Global Burden of Disease Study 2016. Lancet. 2017;390(10100):1345-1422. doi:10.1016/S0140-6736(17)32366-8
- World Health Organization. 7 Million Premature Deaths Annually Linked to Air Pollution.; 2014. http://www.who.int/mediacentre/news/releases/2014/air-pollution/en/.
- World Health Organization. Burden of Disease from Household Air Pollution for 2012: Summary of Results. Geneva, Switzerland; 2012. http://www.who.int/phe/health_topics/outdoorair/databases/FINAL_HAP_AAP_BoD_24March2014.pdf.