A01 Air Quality (WELL v2, Q2 2025)

Concept: Air · Type: Precondition

Intent

Provide a basic level of indoor air quality that contributes to the health and well-being of building users.

Summary

This WELL feature requires projects to provide acceptable air quality levels, as determined by public health authorities.

Issue

Exposure to air pollutants, such as Volatile Organic Compounds (VOCs), ozone, particulate matter, carbon monoxide and others has been shown to increase the risk of respiratory and cardiovascular diseases, in addition to causing thousands of cancer deaths annually.1 Inhaling pollutants presents symptoms including headaches, dry throat, eye irritation and runny nose that may later develop into extreme health outcomes, such as asthma attacks and cancer.2–4 In addition, radon exposure is the second leading cause of lung cancer, after tobacco use.5 Therefore, it is important to define indoor air quality levels that minimize risk to human health. 

Evidence

The World Health Organization (WHO) and other regulatory bodies, such as the U.S. Environmental Protection Agency (EPA) identify a list of “criteria” air pollutants. They have established permissible levels for such criteria pollutants based on epidemiological studies that show the relationships between concentrations of these pollutants, duration of exposure and health risks. Achieving the goal of clean indoor air as defined by permissible levels, requires the joint efforts of both professionals and building users in the implementation of adequate approaches. Indoor air quality can be properly managed through different features listed in the WELL Air concept, including source control strategies, passive and active building design and operation strategies and human behavior interventions. Effective mechanical ventilation is particularly effective at bringing radon below acceptable thresholds.6,7

Requirements

A01.1 Meet Thresholds for Particulate Matter — Precondition

Applies to: All Spaces; excluding Commercial Kitchen Spaces, Industrial.

Meet any one of the following options:

Option 1: Acceptable thresholds

The following thresholds are met in occupiable spaces:

Verification: Performance Test OR Sensor Data

Performance verification: PM2.5 and PM10

Test method:

Device requirements:

Reporting and compliance:

Option 2: Modified thresholds in polluted regions (eligible up to Gold level)

For buildings where the annual average outdoor PM2.5 level is 35 µg/m3 or higher, the following thresholds are met:

Verification: Performance Test OR Sensor Data, Technical Document (Shareable)

Technical Document: A report reflecting annual average PM2.5 levels

Option 3: Dynamic thresholds in polluted regions (eligible up to Silver level)

For buildings where the annual average outdoor PM2.5 level is 35 µg/m3 or higher, the following thresholds are met:

Verification: Performance Test OR Sensor Data, Technical Document (Shareable)

Technical Document: A report reflecting annual average PM2.5 levels

Applies to: Commercial Kitchen Spaces, Industrial.

Meet any one of the following options:

Option 1: Acceptable thresholds

The following threshold is met:

Verification: Performance Test OR Sensor Data

Option 2: Dynamic thresholds in polluted regions (eligible up to Silver level)

For buildings where the annual average outdoor PM2.5 level is 35 µg/m3 or higher, the following thresholds are met:

Verification: Performance Test OR Sensor Data, Technical Document (Shareable)

Technical Document: A report reflecting annual average PM2.5 levels

Multifamily residential projects may achieve WELL Certification at the Bronze or Silver level without testing in dwelling units, but cannot achieve Gold or Platinum without testing in dwelling units. See Sampling Rates for Multifamily Residential in the WELL Performance Verification Guidebook for further details.

The World Health Organization’s Global Urban Ambient Air Pollution Database may be consulted to view outdoor air quality levels, available at https://www.who.int/data/gho/data/themes/air-pollution/who-air-quality-database.

Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations. Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.

WELL Core:

Meet these requirements in non-leased spaces, provided these areas comprise at least 2.5% of the total project area. Otherwise, meet these requirements in non-leased space plus sufficient leased space to sum to 2.5% of the total project area.

A01.2 Meet Thresholds for Organic Gases — Precondition

Applies to: All Spaces.

Meet any one of the following options:

Option 1: Laboratory-based VOC tests

The following thresholds are met in occupiable spaces:

Verification: Performance Test

Performance verification: Formaldehyde and Acetaldehyde

Test method:

Device requirements:

Reporting and compliance:

Performance verification: VOCs (except Formaldehyde and Acetaldehyde)

Test method:

Device requirements:

Reporting and compliance:

Option 2: TVOC continuous monitoring

The following threshold is met in occupiable spaces:

Projects undergoing recertification which were previously awarded Feature A08 must consider all data collected since the previous (re)certification.

Verification: Sensor Data

Multifamily residential projects may achieve WELL Certification at the Bronze or Silver level without testing in dwelling units, but cannot achieve Gold or Platinum without testing in dwelling units. See Sampling Rates for Multifamily Residential in the WELL Performance Verification Guidebook for further details.

Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.

WELL Core:

Meet these requirements in non-leased spaces, provided these areas comprise at least 2.5% of the total project area. Otherwise, meet these requirements in non-leased space plus sufficient leased space to sum to 2.5% of the total project area.

A01.3 Meet Thresholds for Inorganic Gases — Precondition

Applies to: All Spaces; excluding Commercial Kitchen Spaces, Industrial.

The following thresholds are met in occupiable spaces:

Verification: Performance Test OR Sensor Data

Performance verification: Carbon Monoxide

Test method:

Device requirements:

Reporting and compliance:

Performance verification: Ozone

Test method:

Device requirements:

Reporting and compliance:

Applies to: Commercial Kitchen Spaces, Industrial.

The following thresholds are met:

Verification: Performance Test OR Sensor Data

Multifamily residential projects may achieve WELL Certification at the Bronze or Silver level without testing in dwelling units, but cannot achieve Gold or Platinum without testing in dwelling units. See Sampling Rates for Multifamily Residential in the WELL Performance Verification Guidebook for further details.

Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.

WELL Core:

Meet these requirements in non-leased spaces, provided these areas comprise at least 2.5% of the total project area. Otherwise, meet these requirements in non-leased space plus sufficient leased space to sum to 2.5% of the total project area.

A01.4 Meet Thresholds for Radon — Precondition

Applies to: All Spaces.

Meet any one of the following options:

Option 1: Radon testing

The following threshold is met on the lowest regularly occupiable floor:

Verification: Sensor Data, Technical Document (Individual)

Technical Document: Radon test report

Option 2: Mechanical ventilation

For regularly occupied spaces at or below grade, the following requirement is met:

Verification: Letter of Assurance – Engineer

Option 3: Above-grade

One of the following requirements are met in regularly occupied spaces:

Verification: Letter of Assurance – Owner

Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.

WELL Core:

For Option 1, meet these requirements in non-leased spaces at or below grade, provided these areas comprise at least 2.5% of the total project area at or below grade. Otherwise, meet these requirements in non-leased space plus sufficient leased space to sum to 2.5% of the total project area at or below grade. 

For Option 2, meet the requirements in non-leased spaces at or below grade. In leased spaces at or below grade, provide sufficient outdoor air; installation of ducts and diffusers is not required.

For Option 3, meet these requirements in the whole building.

A01.5 Measure Air Parameters — Precondition

Applies to: All Spaces; excluding Dwelling Units.

The following pollutants are monitored in occupiable spaces at intervals no longer than once per year, and the results are submitted annually through the WELL digital platform. To determine the required sample locations and quantity, refer to the WELL Performance Verification Guidebook.

Projects are not required to follow the device requirements or test methods described in the Performance Verification Guidebook. 

Verification: On-going Data Report

WELL Core:

Meet these requirements in non-leased spaces. Calculate the number of samples using the area of non-leased space.

Frequently asked questions

Where can ambient air quality be found so that a project can determine if it is eligible to use the PM limits in options 2 and 3 for Feature A01 Part 1?

One resource projects may use is the World Health Organization’s Global Urban Ambient Air Pollution Database, available at https://www.who.int/data/gho/data/themes/air-pollution/who-air-quality-database.

If a monitoring device with sensors installed to meet A08.1 measures the pollutants listed in A01.1, A01.2, and A01.3, can the monitoring device with sensors installed for A08.1 be used to comply with Feature A01.5?

Yes, monitoring devices with sensors installed for A08.1 can also be used to comply with A01.5 so long as all of the relevant air quality parameters are monitored (TVOCs may be monitored in lieu of formaldehyde, toluene, and benzene). If an individual monitor with sensors cannot monitor all relevant air quality parameters, additional devices or on-site testing will need to be utilized. Note: the number of monitors installed for Feature A08 will likely be higher than the minimum number of test locations in the Performance Verification Guidebook.

For projects that utilize continuous monitors, what data is required to be submitted for on-going data reporting for Part 5?

Projects must provide at least one annual measurement from each monitor for each pollutant listed for a sufficient number of test locations. Monitoring reports which include multiple measurements over regular intervals are acceptable. To determine the required sample locations and quantity, refer to the WELL Performance Verification Guidebook.

I am using sensors installed in my project to meet Feature A01.5; where should I look in the WELL Performance Verification Guidebook to know how many I need to install?

If you are only looking to earn Feature A01.5 and not A08.1 or an Air Concept feature part that will be verified by Sensor Data (i.e., A01.1, A01.2, A01.3, A01.4, A03.1, A05.1, A05.3, A06.1), then you can look in the Quantity of Sample Locations table in the Air section of Performance Testing Requirements. In this case, there are also no requirements for device quality.

If you are looking to also earn Feature A08.1 and / or any Air Concept feature parts verified by Sensor Data, then look in the Monitor Density table in the Continuous Monitoring Requirements section and be sure the monitors meet the device quality requirements in Sensor Technical Specification Requirements for sufficient parameters. 

Does my WELL Core project need to sample in both non-leased and leased spaces for all Feature A01 parts if the project is not pursuing the matching Feature A05 parts?

All projects have the option to only pursue select parts under Feature A05, despite being required to pursue all parts under Feature A01. When determining sample quantities, WELL Core projects may pursue testing in only non-leased spaces for the Feature A01 parts for which they are not pursuing the matching Feature A05 part. Refer to the WELL Performance Verification guidebook for more on sample quantities for WELL Core projects pursuing both Feature A01 and Feature A05, Part 1, 2, or 3.

References

  1. Franklin BA, Brook R, Arden Pope C. Air pollution and cardiovascular disease. Curr Probl Cardiol. 2015;40(5):207-238. doi:10.1016/j.cpcardiol.2015.01.003
  2. Joshi S. The sick building syndrome. Indian J Occup Environ Med. 2008;12(2):61. doi:10.4103/0019-5278.43262
  3. Selgrade MK, Plopper CG, Gilmour MI, Conolly RB, Foos BSP. Assessing the health effects and risks associated with children’s inhalation exposures - Asthma and allergy. J Toxicol Environ Heal - Part A Curr Issues. 2008;71(3):196-207. doi:10.1080/15287390701597897
  4. U.S. Environmental Protection Agency. Indoor Air Pollution: An Introduction for Health Professionals. https://www.epa.gov/indoor-air-quality-iaq/indoor-air-pollution-introduction-health-professionals.
  5. World Health Organization. WHO Handbook on Indoor Radon: A Public Health Perspective. Presented at the: 2009. https://www.who.int/ionizing_radiation/env/9789241547673/en/.
  6. Yang S, Goyette Pernot J, Hager Jörin C, Niculita-Hirzel H, Perret V, Licina D. Radon Investigation in 650 Energy Efficient Dwellings in Western Switzerland: Impact of Energy Renovation and Building Characteristics. Atmosphere (Basel). 2019;10(12):777. doi:10.3390/atmos10120777
  7. Hadlich DE, Grimsrud DT. Radon in Institutional Buildings : The Impacts of Conservation Strategies. Radon Institutional Build Impacts. 1991;(1990).
  8. U.S. Environmental Protection Agency. NAAQS Table. https://www.epa.gov/criteria-air-pollutants/naaqs-table.
  9. European Commission. Proposal for a directive of the European Parliament and of the Council on ambient air quality and cleaner air for Europe - COM(2005) 447 Final. Off J Eur Union. 2005;0183:1-67.
  10. World Health Organization. Air Quality Guidelines for Particulate Matter, Ozone, Nitrogen Dioxide and Sulfur Dioxide. Geneva, Switzerland; 2005. http://apps.who.int/iris/bitstream/handle/10665/69477/WHO_SDE_PHE_OEH_06.02_eng.pdf;jsessionid=CD44465FAC0A1628540C4A2BDF0B51CD?sequence=1.
  11. French Agency for Food Environmental and Occupational Health and Safety. ANSES’s List of Indoor Air Quality Guideline Values.; 2018. https://www.anses.fr/fr/system/files/Tableau_VGAI_Juillet2018EN.pdf.
  12. Health Canada. Residential Indoor Air Quality Guideline: Formaldehyde.; 2006. https://www.canada.ca/content/dam/canada/health-canada/migration/healthy-canadians/publications/healthy-living-vie-saine/formaldehyde/alt/formaldehyde-eng.pdf.
  13. California Office of Environmental Health Hazard Assessment. Acute, 8-hour and Chronic Reference Exposure Level (REL) Summary. https://oehha.ca.gov/air/general-info/oehha-acute-8-hour-and-chronic-reference-exposure-level-rel-summary. Published 2019.
  14. Health and Safety Executive. EH40/2005 Workplace Exposure Limits.; 2011. http://www.hse.gov.uk/pUbns/priced/eh40.pdf.