A13 Enhanced Supply Air (WELL v2, Q2 2025)
Concept: Air · Type: Optimization · Maximum points: 3
Intent
Mitigate risks from indoor contamination and pollution sources, such as infectious disease particles and volatile organic compounds (VOC).
Summary
This WELL feature requires the projects to use supply air that is not recirculated or that is treated with carbon filters, media filters and/or Ultraviolet Germicidal Irradiation (UVGI).
Issue
Building materials, furnishings (e.g., carpets and furniture finishes), fabrics, cleaning products, personal care products, adhesives, solvents and air fresheners can all emit VOCs or semi-volatile organic compounds (SVOCs) into the indoor environment.1,2 VOCs include benzene, formaldehyde and other chemical compounds which, at high concentrations, can lead to the irritation of the nose and pharynx and have been associated with leukemia and nasopharyngeal cancer.3,4 Health effects can also include damage to the liver, kidneys and central nervous system.5 When humans exhale, they can release pathogens, such as COVID-19 or Influenza particles, which can remain suspended in the air for several hours or longer. These pathogens can be recirculated through ducts and HVAC systems of buildings, increasing the risk of transmission of disease indoors.6–8
Evidence
The simplest way to avoid recirculating contaminated air is to not recirculate it by supplying spaces with 100% outdoor air. Unfortunately, in certain climates this can result in high energy usage, although this can be mitigated through the use of heat recovery systems.9 In buildings where recirculated air is utilized, it can be treated to remove contaminants. Carbon is capable of filtering VOCs and ozone from the air that passes through10,11. HEPA or near-HEPA filters can help remove virus particles, since the virus often travels as an attachment to a larger particle.12,13 UVGI systems can also be effective, both when irradiating the upper portion of the room or when installed in the air ducts, so long as they are powerful and/or the air speed is slow enough to provide a sufficient UV dose.13,14 Other technologies exist, but should be evaluated carefully. For example, more novel devices that release oxidants into rooms have less robust evidence for safety and efficacy outside of laboratory conditions.15,16 Finally, in-room air purifiers can be beneficial because the clean air is often provided within the breathing zone. For optimal performance, air filtration systems need to be maintained according to the manufacturer’s instructions.
Requirements
A13.1 Improve Supply Air — 1 point
Applies to: All Spaces.
Meet any one of the following options:
Option 1: 100% Outdoor air provisions
The following requirements are met:
Each regularly occupied space is ventilated with outdoor air that has not recirculated from other rooms within the building.
Verification: Technical Document (Audited)
Mechanical Drawing
Option 2: Cleaning and purification devices
All regularly occupied spaces with recirculated air are treated with purification/cleaning system(s), either in the HVAC system or as a standalone device, which meet the following requirements:
Use, at a minimum, two of the following air purification/cleaning technologies:
- Activated carbon filter.
- Media filter with an average removal efficiency of ≥75% for particles 0.3-1 µm in size (e.g., MERV 14; F8; ePM1 75%).
- UVGI to treat the moving air OR upper-room UVGI.
Comply with one of the following:
- Are validated under UL 2998 Zero Ozone Emissions Validation or Intertek Zero Ozone Verification.15
- Do not use electronic air cleaners.
Are not designed to release ions, reactants, or other molecules into occupiable spaces to disinfect or clean the air.16
Are sized appropriately to the room volume or area, based on manufacturer specifications.
Are maintained according to the manufacturer’s recommendations. Documentation of maintenance is submitted annually through the WELL digital platform.
Verification: On-site Photographs, Letter of Assurance – Engineer, On-going Maintenance Report
Photographs should showcase:
1) The installed carbon filters, media filters and/or UV treatment devices taken when UV lamps are not in operation, as applicable. (It is not necessary to include filter rating labels in photographs.)
OR
2) The standalone air purification devices.
For situations where projects have restricted access to the installed filters, provide photographs of each type of spare/replacement filter.
Quantity:
1) For HVAC systems: at least one photograph of each type of carbon filter, media filter and/or UV treatment device, as installed.
2) For standalone units: at least 10% of standalone units, up to a maximum of five units.
WELL Core:
Meet these requirements in the whole building. Up to 10% of the total area occupied by tenants can be excluded from the feature scope.A13.2 β Provide Clean Airflow Rates for Control of Infectious Aerosols — 2 points
Applies to: All Spaces.
Meet any one of the following options:
Option 1: Regular Airflow Operation
The mechanical system provides all regularly occupied spaces with clean airflow rates for infection risk management as set in one of the following guidelines:
ASHRAE 241-2023 Table 5-1 Equivalent Clean Airflow Rates (Section 6 - Clean Airflow Rate Equation or Appendix C - In-place Modeling Method).17
5 Equivalent Air Changes per hour (5 e/ACH) calculated in accordance with Appendix A1.18
Verification: Technical Document (Audited), Beta Feature Feedback Form
Mechanical Drawing or Test Report demonstrating clean air flow rates
Option 2: Operation Under Infectious Disease Management Mode
The following requirements are met:
The mechanical system is capable of providing all regularly occupied spaces with clean airflow rates for infection risk management as set in one of the following guidelines:
- ASHRAE 241-2023 Table 5-1 Equivalent Clean Airflow Rates (Section 6 - Clean Airflow Rate Equation or Appendix C - In-place Modeling Method).17
- 5 Equivalent Air Changes per hour (5 e/ACH) calculated in accordance with Appendix A1.18
The project has an operational plan for Infection Risk Management Mode (IRMM) that includes the following:17
- The conditions under which the IRMM will be activated.
- The engineering controls (e.g., changes in ventilation or air treatment) and non-engineering controls (e.g., changes in occupancy) that will be utilized to achieve the target clean airflow rates.
- The operational and maintenance procedures in place to implement target clean airflow rates within 48-hours of the decision to activate IRMM.
- An inventory of HVAC system consumables (e.g., filters, adsorption media, UV bulbs) that is updated when significant equipment modifications have been implemented or after replacement consumables have been utilized.
- A requirement that there is at least one set of replacement consumables available to install during IRMM.
Verification: Technical Document (Audited), Policy and/or Operations Schedule, Beta Feature Feedback Form
Mechanical Drawing or Test Report demonstrating clean air flow rates.
Policy Document and/or Operations Schedule describing Infection Risk Management Mode (IRMM) plans.
This feature is a beta strategy and has an additional documentation requirement (beta feature feedback form). The feedback form supports IWBI in developing new features that are effective and applicable to projects around the world.
WELL Core:
Meet these requirements in the whole building. Up to 10% of the total area occupied by tenants can be excluded from the feature scope.
Frequently asked questions
Are mechanical systems that heat and cool the air locally (e.g., fan-coil units, mini-splits, variable refrigerant flow units) considered systems that recirculate air? Can they be used to meet Option 1 of Improve Supply Air?
Mechanical systems that heat and cool the air locally are not considered systems that recirculate air if they:
• Are only used for thermal control
• Do not move air between rooms
Thus, a project using such systems may still be considered to utilize 100% outdoor air and meet Option 1 of Improve Supply Air.
References
- Salthammer T. Emissions of Volatile Organic Compounds from Products and Materials in Indoor Environments. Handb Environ Chem. 2004;4:37-71. doi:10.1007/b94830
- Wallace LA, Pellizzari E, Leaderer B, Zelon H, Sheldon L. Emissions of volatile organic compounds from building materials and consumer products. Atmos Environ. 1987;21(2):385-393. doi:10.1016/0004-6981(87)90017-5
- Nurmatov UB, Tagiyeva N, Semple S, Devereux G, Sheikh A. Volatile organic compounds and risk of asthma and allergy: A systematic review. Eur Respir Rev. 2015;24(135):92-101. doi:10.1183/09059180.00000714
- Nielsen GD, Larsen ST, Wolkoff P. Re-evaluation of the WHO (2010) formaldehyde indoor air quality guideline for cancer risk assessment. Arch Toxicol. 2017;91(1):35-61. doi:10.1007/s00204-016-1733-8
- U.S. Environmental Protection Agency. Volatile Organic Compounds’ Impact on Indoor Air Quality. https://www.epa.gov/indoor-air-quality-iaq/volatile-organic-compounds-impact-indoor-air-quality.
- Stariolo DA. COVID-19 in Air Suspensions.; 2020. https://arxiv.org/abs/2004.05699. Accessed June 15, 2020.
- Federation of European Heating Ventilation and Air-Conditioning Associations. How to operate and use building services in order to prevent the spread of the coronavirus disease (COVID-19) virus (SARS-CoV-2) in workplaces. 2020.
- Dietz L, Horve PF, Coil DA, Fretz M, Eisen JA, Van Den Wymelenberg K. 2019 Novel Coronavirus (COVID-19) Pandemic: Built Environment Considerations To Reduce Transmission. Gilbert JA, ed. mSystems. 2020;5(2):e00245-20. doi:10.1128/mSystems.00245-20
- Zemitis J, Borodinecs A. Energy saving potential of ventilation systems with exhaust air heat recovery. IOP Conf Ser Mater Sci Eng. 2019;660:012019. doi:10.1088/1757-899X/660/1/012019
- Fisk WJ, Spears M, Sullivan DP, Mendell M. Ozone Removal by Filters Containing Activated Carbon: A Pilot Study.; 2009. https://www.osti.gov/scitech/servlets/purl/1050670/.
- Sekine Y, Fukuda M, Takao Y, Ozano T, Sakuramoto H, Wang KW. Simultaneous removal of formaldehyde and benzene in indoor air with a combination of sorption- and decomposition-type air filters. Environ Technol. 2011;33(15-16):1983-1989. doi:10.1080/09593330.2011.562924
- Liu Y, Ning Z, Chen Y, et al. Aerodynamic analysis of SARS-CoV-2 in two Wuhan hospitals. Nature. 2020. doi:10.1038/s41586-020-2271-3
- The American Society of Heating Refrigerating and Air-Conditioning Engineers. ASHRAE Position Document on Infectious Aerosols. 2020.
- Yang Y, Zhang H, Nunayon SS, Chan V, Lai AC. Disinfection efficacy of ultraviolet germicidal irradiation on airborne bacteria in ventilation ducts. Indoor Air. 2018;28(6):806-817. doi:10.1111/ina.12504
- U.S. Environmental Protection Agency. Air Cleaners, HVAC Filters, and Coronavirus (COVID-19). Accessed: October 7, 2022. https://www.epa.gov/coronavirus/air-cleaners-hvac-filters-and-coronavirus-covid-19
- ASHRAE. ASHRAE Position Document on Filtration and Air Cleaning. Published: 2015. https://www.ashrae.org/file%20library/about/position%20documents/filtration-and-air-cleaning-pd-feb.2.2021.pdf
- American Society of Heating Refrigerating and Air-Conditioning Engineers. ASHRAE 241-2023: Control of Infectious Aerosols.; 2023.
- Centers for Disease Control and Prevention. How Much Ventilation is Enough? https://www.cdc.gov/niosh/ventilation/prevention/Aim-for-5.html.