A06 Enhanced Ventilation Design (WELL v2, Q2 2025)

Concept: Air · Type: Optimization · Maximum points: 3

Intent

Expel internally generated pollutants and improve air quality in the breathing zone through an increased supply of outdoor air or increased ventilation efficiency.

Summary

This WELL feature requires implementation of advanced ventilation strategies that can achieve higher air quality levels and thus benefit human health and productivity.

Issue

The majority of ventilation standards specify ventilation rates and other measures intended to provide indoor air quality that is merely “acceptable” to building users and reduces the risk of adverse health effects.1 Even with proper ventilation designed to meet ventilation standards, the concentration of indoor pollutants can exceed concentrations found in outdoor air.2,3 Ventilation rates less than {{well-unit}}21 cfm|10 L/s{{/well-unit}} per person in all building types are associated with negative perception of air quality and actual health outcomes.4

Evidence

Scientific research suggests that an airflow rate significantly exceeding that recommended by standards is needed to minimize sick building syndrome symptoms and to improve human performance and productivity.5,6 Since it is difficult to test for every potential pollutant, and because carbon dioxide (CO2) is easy to detect, CO2 levels serve as a proxy for other indoor pollutants. A number of CO2 studies suggest that the risk of sick building syndrome symptoms decreases significantly, when CO2 concentrations are less than 800 ppm.4 One method for decreasing the CO2 concentration experienced by occupants while minimizing additional energy use is demand-controlled ventilation, in which the delivery rate for outside air is directly linked to the measured CO2 levels within the space.7 Displacement ventilation improves indoor air quality, by delivering fresh outdoor air at the floor level, leaving warmer polluted indoor air, such as CO2 to be extracted above the height of the ventilation zone.8

Requirements

A06.1 Increase Outdoor Air Supply — 1–2 points (max 2)

Applies to: All Spaces.

Meet any one of the following options:

Option 1: Increased air supply

For mechanically ventilated buildings, the following requirement is met in all occupiable spaces:

Verification: Letter of Assurance – Engineer

Option 2: Demand control ventilation

For mechanically ventilated buildlings, the following requirements are met in at least 90% of regularly occupied spaces:

Verification: Letter of Assurance – Engineer

Option 3: Enhanced natural ventilation

For naturally ventilated buildings, the following requirement is met:

Verification: Technical Document (Audited)

Modeling report or room-by-room CO2 calculations

Option 4: Ventilation monitoring

One of the following carbon dioxide thresholds is met in occupiable spaces:

This Option is worth {{well-points}}2|3{{/well-points}} points.

Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.

Verification: Sensor Data

Mixed-mode projects must select the option corresponding to the ventilation mode (mechanical and natural ventilation) in operation for the majority of operating hours within the year.

WELL Core:

Meet these requirement in the whole building. If the project pursues Option 1 or Option 2, it must provide leased spaces with sufficient outdoor air and a compatible control system (as applicable) but is not required to install ducts and diffusers within leased spaces.

A06.2 Improve Ventilation Effectiveness — 1 point

Applies to: All Spaces.

Meet any one of the following options:

Option 1: Displacement ventilation system

The project uses a displacement ventilation system in at least 90% of regularly occupied spaces, with one of the following as a basis for design:

Verification: Letter of Assurance – Engineer

Option 2: Personalized ventilation system

At least 50% of workstations incorporate personalized ventilation systems that meet the following requirements:

Verification: Letter of Assurance – Engineer

WELL Core:

Meet these requirements in the whole building.

Frequently asked questions

If a mechanical system can achieve ventilation rates 30% or 60% above ASHRAE requirements when in highest operational mode, is this sufficient to meet the feature requirement?

No, to meet the feature requirement the typical operating schedule and settings for the system would need to achieve ventilation rates 30% (for 1 point) or 60% (for 2 points) above ASHRAE.

References

1. Allen JG, Bernstein A, Cao X, et al. The 9 Foundations of a Healthy Building. Sch Public Heal. 2017:35.
2. Parthasarathy, Srinandini, William J. Fisk TEM. Effect Of Ventilation On Chronic Health Risks In Schools And Offices. Berkeley, CA; 2013. https://eta.lbl.gov/sites/all/files/publications/lbnl-6121e.pdf.
3. Shendell DG, Winer AM, Weker R, Colome SD. Evidence of inadequate ventilation in portable classrooms: Results of a pilot study in Los Angeles County. Indoor Air. 2004;14(3):154-158. doi:10.1111/j.1600-0668.2004.00235.x
4. Seppänen OA. Association of ventilation rates and CO2concentrations with health and other responses in commercial and institutional buildings. Indoor Air. 1999;9(4):226-252. doi:10.1111/j.1600-0668.1999.00003.x
5. Wyon DP. The effects of indoor air quality on performance and productivity. Indoor Air, Suppl. 2004;14(SUPPL. 7):92-101. doi:10.1111/j.1600-0668.2004.00278.x
6. Sundell J, Levin H, Nazaroff WW, et al. Ventilation rates and health: Multidisciplinary review of the scientific literature. Indoor Air. 2011;21(3):191-204. doi:10.1111/j.1600-0668.2010.00703.x
7. U.S. Department of Energy. Demand Control Ventilation. 2012.
8. Wang Y, Kuckelkorn J, Zhao FY, Spliethoff H. Indoor environment of a classroom in a passive school building with displacement ventilation. Proc BS 2013 13th Conf Int Build Perform Simul Assoc. 2013:1902-1909.
9. American Society of Heating Refrigerating and Air-Conditioning Engineers. Performance Evaluation and Development of Design Guidelines for Displacement Ventilation, RP-949.; 1998.
10. American Society of Heating Refrigerating and Air-Conditioning Engineers. ASHRAE 62.1-2019: Ventilation for Acceptable Indoor Air Quality. 2019.
11. Skistad H, Mundt E, Nielsen P V., Hagstrom K, Railio J. Displacement Ventilation in Non-Industrial Premises. REHVA Guidebook No. 1. Rehva; 2002.