A11 Source Separation (WELL v2, Q2 2025)

Concept: Air · Type: Optimization · Maximum points: 1

Intent

Preserve indoor air quality and maximize olfactory comfort in occupied spaces through the isolation and proper ventilation of indoor pollution sources and chemical storage areas.

Summary

This WELL feature requires strategies that isolate key sources of odors, germs, pollution or humidity through doors or dedicated exhaust.

Issue

Air pollution can be created from many indoor sources, including cleaning products, office equipment and humid environments. Chemical storage closets that house cleaning products, can be a source of harmful vapors, including Volatile Organic Compounds (VOCs) that are linked to cancer, organ and central nervous system damage.1,2 Copy rooms can contribute to the production of ozone, which has been associated with lung inflammation, chest pain, wheezing, coughing, shortness of breath and the exacerbation of respiratory illnesses, such as pneumonia and asthma.3–5 Bathrooms can encourage the growth of mold and mildew, which have been associated with allergic reactions and aggravate lung diseases, such as asthma.6 Exposure to air pollutants in kitchens, such as particulate matter, VOCs and polycyclic aromatic hydrocarbons, has been associated with kidney inflammation.7

Evidence

The most effective way to curb air pollution in buildings is to eliminate individual sources or capture emissions at the source, before they spread to surroundings.8 For air pollution sources that are inevitable, physical separation of such sources combined with direct ventilation exhaust systems is an effective means of protecting individuals.   

Requirements

A11.1 Manage Pollution and Exhaust — 1 point

Applies to: All Spaces; excluding Dwelling Units, Guest Rooms.

For all bathrooms, kitchens, rooms for cleaning and chemical storage, rooms with high-volume printers and copiers and high-humidity areas, the following requirements are met:

Verification: Technical Document (Audited)

Mechanical drawings

Applies to: Commercial Kitchen Spaces.

Meet any one of the following options:

Option 1: Control cooking pollution

The following requirements are met:

Verification: On-site Photographs, Letter of Assurance – Engineer

Photographs should showcase:
1) The canopy hoods, exhaust systems and overhangs.
2) A measurement tape confirming the vertical distance between the lower lip of the hood and the cooking surface.

Quantity: 
At least one photograph of each relevant appliance from within at least one kitchen.

Option 2: No applicable commercial appliances

The following requirements are met:

Verification: Letter of Assurance – Engineer

Applies to: Dwelling Units, Guest Rooms.

The following requirements are met:

Verification: On-site Photographs, Letter of Assurance – Engineer

Photographs for kitchen exhaust should showcase either: 
1) The range hood and exhaust ductwork to the outdoors. It is not necessary to photograph the entire duct pathway, but the photograph(s) provided should clearly indicate that the range hood is vented and that air is not recirculating in the occupiable space.
2) The space with no cooking burners and stove top appliances. 

Photographs for bathroom exhaust should showcase either:  
1) An operable window. 
2) An exhaust fan. 

Quantity: 
1) At least 10% of dwelling units/guest rooms, up to a maximum of five units.

WELL Core:

Meet these requirements in non-leased spaces. To earn an additional point, meet these requirements in all leased spaces.

WELL Core projects where non-leased space represents 40% or more of total project area may pursue the additional point without achieving the feature requirements in tenant spaces. Projects utilizing this pathway should include a note on the documentation required by the feature.    

Frequently asked questions

Can a project increase the supply of fresh air into the required spaces in lieu of exhausting the air in a space so that all air is expelled rather than recirculated?

No, while having additional fresh air will dilute the pollution, it does not ensure pollution isolation. Therefore, all air including bathrooms should be exhausted rather than recirculated.

Is it acceptable for the ventilation system to return air to the heat exchanger to extract heat before expelling the air?

Yes, this is acceptable so long as there will be no contact between the return air and outdoor air. 

Are office kitchenettes included within the scope of this feature?

Yes, kitchenettes are considered kitchens (and hence within scope) if there is a device for heating or reheating food, such as a microwave. If there is no device for heating or reheating food, the space would not be considered within scope. For example, pantries with snacks or coffee and seating for dining areas are not considered kitchens.

How would a hotel meet this feature?

For the purposes of this feature, the "dwelling unit and guest room" requirements should be met in all guest rooms if the appliances are provided. All other hotel spaces should adhere to the requirements for "All other spaces except dwelling units & guest rooms" or "commercial kitchens", as applicable.

References

  1. Nurmatov UB, Tagiyeva N, Semple S, Devereux G, Sheikh A. Volatile organic compounds and risk of asthma and allergy: A systematic review. Eur Respir Rev. 2015;24(135):92-101. doi:10.1183/09059180.00000714
  2. U.S. Environmental Protection Agency. Volatile Organic Compounds’ Impact on Indoor Air Quality. https://www.epa.gov/indoor-air-quality-iaq/volatile-organic-compounds-impact-indoor-air-quality.
  3. U.S. Environmental Protection Agency. Health Effects of Ozone in Patients with Asthma and Other Chronic Respiratory Disease. https://www.epa.gov/ozone-pollution-and-your-patients-health/health-effects-ozone-patients-asthma-and-other-chronic.
  4. The National Institute of Environmental Health Sciences. Ozone. https://www.niehs.nih.gov/health/topics/agents/ozone/index.cfm. Published 2008.
  5. Tuomi T, Engstrom B, Niemela R, Svinhufvud J, Reijula K. Emission of ozone and organic volatiles from a selection of laser printers and photocopiers. Appl Occup Environ Hyg. 2000;15(8):629-634. doi:10.1080/10473220050075635
  6. Mendell MJ, Mirer AG, Cheung K, Tong M, Douwes J. Respiratory and allergic health effects of dampness, mold, and dampness-related agents: A review of the epidemiologic evidence. Environ Health Perspect. 2011;119(6):748-756. doi:10.1289/ehp.1002410
  7. Singh A, Kamal R, Mudiam MKR, et al. Heat and PAHs emissions in indoor kitchen air and its impact on kidney dysfunctions among kitchen workers in Lucknow, North India. Jia Z, ed. PLoS One. 2016;11(2):e0148641. doi:10.1371/journal.pone.0148641
  8. U.S. Environmental Protection Agency. Improving Indoor Air Quality. https://www.epa.gov/indoor-air-quality-iaq/improving-indoor-air-quality.
  9. U.S. Green Building Council. LEED BD+C: New Construction | v4 - LEED v4. 2018. https://www.usgbc.org/sites/default/files/LEED v4 BDC_07.2.18_current.pdf.
  10. Wenger Corporation. Planning your athletic facility. https://www.wengercorp.com/Construct/docs/Athletic Planning Guide by Wenger GearBoss.pdf.
  11. California Energy Commission. Design Guide Improving Commercial Kitchen Ventilation System Performance.; 2003. http://www.energy.ca.gov/reports/2003-06-13_500-03-034F.PDF.
  12. International Codes Council. 2015 Minnesota Mechanical and Fuel Gas Code with the ANSI/ASHRAE Standard 154-2011. Presented at the: 2015. https://codes.iccsafe.org/public/document/MMFGC2015/copyright.
  13. American Society of Heating Refrigerating and Air-Conditioning Engineers. ASHRAE 90.1: Energy Standard for Buildings Except Low-Rise Residential Buildings.; 2010. http://www.usailighting.com/stuff/contentmgr/files/1/b90ce247855d0f17438484c003877338/misc/ashrae_90_1_2010.pdf.
  14. American Society of Heating Refrigerating and Air-Conditioning Engineers. ASHRAE 189.1: Standard for the Design of High-Performance Green Buildings Except Low-Rise Residential Buildings.; 2011. http://www.ditar.cl/archivos/Normas_ASHRAE/T1160ASHRAE-189.1-2009-Design-H-P-Green-Buildings.pdf.
  15. Sobiski P, Swierczyna R, Fisher D. Effects of Range Top Diversity, Range Accessories, and Hood Dimensions on Commercial Kitchen Hood Performance. Vol 112 PART 1. San Francisco, CA; 2006.
  16. Militello-Hourigan RE, Miller SL. The impacts of cooking and an assessment of indoor air quality in Colorado passive and tightly constructed homes. Build Environ. 2018. doi:10.1016/j.buildenv.2018.08.044
  17. American Society of Heating Refrigerating and Air Conditioning Engineers (ASHRAE). ASHRAE 154-2003: Ventilation for Commercial Cooking Operations. 2003. http://sspc154.ashraepcs.org/pdf/STD154_2003.pdf.
  18. Home Ventilating Institute. What is a range hood? https://www.hvi.org/HVIORG/document-server/?cfp=HVIORG/assets/File/public/publications/HVIRangeHood_4Feb08.pdf.
  19. Singer BC, Delp WW, Apte MG. Experimental evaluation of installed cooking exhaust fan performance. Ernest Orlando Lawrence Berkeley Natl Lab. 2012.