A07 Operable Windows (WELL v2, Q2 2025)
Concept: Air · Type: Optimization · Maximum points: 2
Intent
Increase the supply of high-quality outdoor air and promote a connection to the outdoor environment, by encouraging building users to open windows when outdoor air quality is acceptable.Summary
This WELL feature requires buildings with operable windows to increase the supply of high-quality outdoor air and promote a connection to the outdoor environment, by encouraging building users to open windows when outdoor air quality is acceptable.Issue
Inhalation of harmful indoor substances is correlated with adverse health outcomes, such as infectious diseases, cancer, asthma, allergies and other respiratory infections.1,2 When outdoor air quality is favorable, opening windows can provide a supply of outdoor air and lower levels of indoor air contaminants. Achieving natural ventilation through open windows can provide a positive human experience.3 However, it is challenging to the ability to maintain strict control over interior air quality. Despite often having conditions of temperature and ventilation below recommended standards, studies have shown that naturally ventilated buildings have fewer people reporting sick building syndrome symptoms than mechanically conditioned buildings.4,5 In addition, studies have shown that there is a 7.7% productivity benefit associated with naturally ventilated spaces.5,6Evidence
When weather and local outdoor parameters indicate high-quality outdoor air, people should be encouraged to make use of natural ventilation strategies. However, ventilating through windows generally introduces more outdoor pollution than mechanical systems with filters.7 Human behavior is rated as one of the top three components affecting the generation and persistence of indoor air pollutants.7 Educating and informing building users when outdoor conditions are favorable for window opening, can reduce the generation and persistence of indoor air pollutants.Requirements
A07.1 Provide Operable Windows — 1 point
Applies to: All Spaces.
Project meets one of the below:
At least 75% of the regularly occupied spaces have operable windows that provide access to outdoor air.
For each floor, the openable window area is at least 4% the area of the indoor occupiable space.
The World Health Organization’s Global Urban Ambient Air Pollution Database may be consulted to view outdoor air quality levels, available at https://www.who.int/data/gho/data/themes/air-pollution/who-air-quality-database
Verification: On-site Photographs, Letter of Assurance – Designer
Photographs should showcase:
1) The window in the open position.
2) The mechanism used to open the window.
Quantity: At least 10% of operable windows, up to a maximum of five windows. Photographs should be distributed throughout the project and across different types of operable windows, as applicable.
Projects where the average outdoor PM2.5 level is 35 µg/m³ or higher may only achieve Part 1: Provide Operable Windows in conjunction with Part 2: Manage Window Use.
WELL Core:
Meet these requirements in the whole building. For area calculations, projects may use assumptions of regularly occupied spaces in leased spaces.A07.2 Manage Window Use — 1 point
Applies to: All Spaces.
Meet all of the following options:
Option 1: Outdoor air measurement
The following requirement is met:Outdoor levels of PM2.5, temperature and humidity are monitored at intervals of at least once per hour, based on a data-gathering station located within {{well-unit}}2.5 mi|4 km{{/well-unit}} of the building. This monitoring system may be operated by the project or by another entity (e.g., a government).
Verification: Professional Narrative
Option 2: Window operation
Indicator lights and/or digital displays at windows (at least one per room with windows) cue occupants when conditions outside are suitable for opening windows:
PM2.5: 15 µg/m³ or lower.
Dry-bulb temperature: within {{well-unit}}15 °F|8 °C{{/well-unit}} of indoor air temperature setpoint.
Relative Humidity: 65% or lower.
Verification: On-site Photographs, Letter of Assurance – Engineer
Photographs should showcase:
1) The indicator method.
Quantity: At least 10% of windows with an indicator, up to a maximum of five windows. Photographs should be distributed throughout the project and across different types of indicators, as applicable.
Projects may only achieve this part if Part 1 is also achieved.
WELL Core:
Meet these requirements in the whole building.Frequently asked questions
How is the openable window area calculated?
For hung and sliding windows, use the area of the opening. For hinged windows (e.g., casement, awning), use the minimum of 1) the area of the window or 2) the sum of the geometric shapes created between window edges and opening (e.g., one square and two triangles).
How do you determine the area of regularly occupied spaces with operable windows?
Use the total area of an interior space with at least one operable window. There are no proximity requirements from operable windows within an interior space. Spaces divided by interior doors and walls must be treated as separate space. (i.e., the entire area of a 100 m2 open office space with one window can be counted towards feature requirements. Private offices and meeting rooms separated by doors and walls must have operable windows to be counted towards feature requirements).
References
- Douwes J, Thorne P, Pearce N, Heederik D. Bioaerosol health effects and exposure assessment: Progress and prospects. Ann Occup Hyg. 2003;47(3):187-200. doi:10.1093/annhyg/meg032
- Selgrade MK, Plopper CG, Gilmour MI, Conolly RB, Foos BSP. Assessing the health effects and risks associated with children’s inhalation exposures - Asthma and allergy. J Toxicol Environ Heal - Part A Curr Issues. 2008;71(3):196-207. doi:10.1080/15287390701597897
- Brager GS. Benefits of Improving Occupant Comfort and Well-being in Buildings. In: Proceedings of the 4th International Holcim Forum for Sustainable Construction: The Economy of Sustainable Construction. Mumbai; 2013:181–194. https://src.lafargeholcim-foundation.org/dnl/93603859-d59e-498a-b056-405d16e39171/F13_OrangeWS_Brager.pdf.
- Burge S, Hedge A, Wilson S, Bass JH, Robertson A. Sick building syndrome: A study of 4373 office workers. Ann Occup Hyg. 1987;31(4 A):493-504. doi:10.1093/annhyg/31.4A.493
- Horr, A., Kaushik, A., Mazroei, A., Katafygiotou, A. & Elsarrag E. Occupant productivity and office indoor environment quality : a review of the literature Occupant Productivity and Office Indoor Environment Quality : A Review of the Literature. 2016. http://usir.salford.ac.uk/39106/3/BAE-D-16-00533_final%2520manuscript%5B1%5D.pdf.
- Wargocki P, Wyon DP, Fanger PO. Productivity is affected by the air quality in offices. Proc Heal Build 2000. 2000;1:635-640.
- Nazaroff WW. Exploring the consequences of climate change for indoor air quality. Environ Res Lett. 2013. doi:10.1088/1748-9326/8/1/015022
- American Society of Heating Refrigerating and Air-Conditioning Engineers. ASHRAE 62.1-2010: Ventilation for Acceptable Indoor Air Quality.; 2010.