Thermal Comfort concept (WELL v2, Q2 2025)
Intent
The WELL Thermal Comfort concept aims to promote human productivity and provide a maximum level of thermal comfort among all building users through improved HVAC system design and control and by meeting individual thermal preferences.
Background
The WELL Thermal Comfort concept aims to promote human productivity and provide a maximum level of thermal comfort among all building users through improved HVAC system design and control and by meeting individual thermal preferences.
Thermal comfort is defined as “the condition of mind that expresses satisfaction with the thermal environment and is assessed by subjective evaluation."1 Thermal comfort greatly influences our experiences in the places where we live and work2 and is one of the highest contributing factors influencing overall human satisfaction in buildings3–5 impacting individual levels of motivation, alertness, focus and mood.5 Its influence on the integumentary, endocrine and respiratory systems also allows thermal comfort to play a large role in our health, well-being and productivity. Beyond the scope of individual impact, the indoor thermal environment also impacts a buildings’ energy use, since cooling and heating in developed and many developing countries account for approximately half of a building’s energy consumption. 6,7
Despite technological advancements, great improvements in our understanding of thermal comfort in buildings and existing standards establishing specific criteria indicating buildings should provide an acceptable thermal environment for a minimum 80% of occupants,8 many people still feel uncomfortable during the work day.9,10 In fact, studies have shown only 11% of the office buildings surveyed in the U.S. provided thermal environments that met accepted goals of human satisfaction.11 Moreover, as many as 41% of office workers have expressed dissatisfaction with their thermal environment.11 Such levels of dissatisfaction may be detrimental not only to the individual but also the business at large, since leading research indicates that employees perform on average 15% poorer in hot conditions and on average 14% poorer in cold conditions.12 In contrast to those who are dissatisfied with thermal conditions, office workers who are satisfied with their thermal environment can be more productive in the workplace.11
Thermal comfort is subjective, which means that not everyone will be comfortable under the same conditions. This highlights that a one-size-fits-all approach to thermal comfort in buildings invariably fails for large numbers of people.13 A comfortable thermal environment that satisfies all occupants is challenging to achieve, due to individual preferences and possible spatial and temporal variations in the thermal environment.14 There is a need for a holistic approach to thermal comfort that can satisfy the individual preferences of all (or nearly all) building users. When possible, personal thermal comfort devices should be used. These have been shown to improve self-reported productivity rates, decrease symptoms associated with sick building syndrome and increase thermal comfort.15 However, due to the difficulties of setting temperature levels that suit all individual preferences,1 thermal comfort conditions should create baseline satisfaction for the largest number of people. Overall, systems should always be designed with human-centric thermal zoning in mind, helping to optimize the system’s thermal performance.16
The WELL Thermal Comfort concept takes a holistic approach to thermal comfort and provides a combination of research-based interventions to help design buildings that address individual thermal discomfort and support human health, well-being and productivity.
Features in the Thermal Comfort concept (WELL v2, Q2 2025)
- T01 Thermal Performance — Precondition
- T02 Verified Thermal Comfort — Optimization
- T03 Thermal Zoning — Optimization
- T04 Individual Thermal Control — Optimization
- T05 Radiant Thermal Comfort — Optimization
- T06 Thermal Comfort Monitoring — Optimization
- T07 Humidity Control — Optimization
- T08 β Enhanced Operable Windows — Optimization
- T09 β Outdoor Thermal Comfort — Optimization
Note
Read more about the evidence behind the WELL Thermal Comfort Concept. Note: Material from the research digests is not covered on the WELL AP exam.
Testing location
- Sampling points must be representative of typical occupied areas within the sampling zone.
- Sampling points must be located at least 1 m [3.3 ft] away from windows, walls, doors, direct sunlight, air supply/exhausts, mechanical fans, heaters or any other significant source of heat or cold. To the extent possible, sampling points should be at least 5 m [16.4 ft] from exterior doors.
- For projects with multiple floors, the measurements must be distributed across different floors, including the lowest and the highest regularly occupied floor.
- The measurements must be conducted at various locations across the building floor area, including both interior space and in proximity to façades with different orientations.
Sampling quantity
- Measurements are recorded in 8% of the total number of each regularly occupied room type in the project (at least one of each room type).
- For Multifamily Residential projects, unless otherwise stated, sample points should be taken as follows:
- Projects with 10 dwelling units or fewer: two of each unit type
- Projects with more than 10 dwelling units: 5% of each unit type, with a minimum of three and a maximum of 40 units of each unit type
- To determine the test quantity for all other non-dwelling spaces, follow Table 2 sampling point guidance for the total area of regularly occupied spaces only, not the total project area (e.g., occupied lobbies and gyms are considered regularly occupied spaces and therefore would be included in the Table 2 calculations; common areas such as hallways are not considered regularly occupied spaces and therefore would not be included in the calculations).
References
- American Society of Heating Refrigerating and Air-Conditioning Engineers. ASHRAE 55-2013: Thermal Environmental Conditions for Human Occupancy. 2013. https://www.techstreet.com/ashrae/standards/ashrae-55-2013?product_id=1868610.
- Nicol JF, Humphreys MA. Adaptive thermal comfort and sustainable thermal standards for buildings. Energy Build. 2002;34(6):563-572. doi:10.1016/S0378-7788(02)00006-3
- Frontczak M, Wargocki P. Literature survey on how different factors influence human comfort in indoor environments. Build Environ. 2011;46(4):922-937. doi:10.1016/j.buildenv.2010.10.021
- Frontczak M, Schiavon S, Goins J, Arens E, Zhang H, Wargocki P. Quantitative relationships between occupant satisfaction and satisfaction aspects of indoor environmental quality and building design. Indoor Air. 2012;22(2):119-131. doi:10.1111/j.1600-0668.2011.00745.x
- Lamb S, Kwok KCS. A longitudinal investigation of work environment stressors on the performance and wellbeing of office workers. Appl Ergon. 2016;52:104-111. doi:10.1016/j.apergo.2015.07.010
- Chua KJ, Chou SK, Yang WM, Yan J. Achieving better energy-efficient air conditioning - A review of technologies and strategies. Appl Energy. 2013;104:87-104. doi:10.1016/j.apenergy.2012.10.037
- Pérez-Lombard L, Ortiz J, Pout C. A review on buildings energy consumption information. Energy Build. 2008;40(3):394-398. doi:10.1016/j.enbuild.2007.03.007
- Kim J, Schiavon S, Brager G. Personal comfort models – A new paradigm in thermal comfort for occupant-centric environmental control. Build Environ. 2018;132:114-124. doi:10.1016/j.buildenv.2018.01.023
- Schiller G, Arens E, Bauman F, Benton C, Fountain M, Doherty T. A field study of thermal environments and comfort in office building. ASHRAE Trans. 1988;94 Part 2.
- Putra JCP. A Study of Thermal Comfort and Occupant Satisfaction in Office Room. Procedia Eng. 2017;170:240-247. doi:10.1016/J.PROENG.2017.03.057
- Huizenga C, Abbaszadeh S, Zagreus L, Arens EA. Air Quality and Thermal Comfort in Office Buildings: Results of a Large Indoor Environmental Quality Survey. In: Proceedings of Healthy Buildings. Vol III. ; 2006:393-397. http://escholarship.org/uc/item/7897g2f8;jsessionid=CEA1E13173D8003D5F74BD638E71785C.
- Vimalanathan K, Babu TR. The effect of indoor office environment on the work performance, health and well-being of office workers. J Environ Heal Sci Eng. 2014;12(1). doi:10.1186/s40201-014-0113-7
- Djongyang N, Tchinda R, Njomo D. Thermal comfort: A review paper. Renew Sustain Energy Rev. 2010;14(9):2626-2640. doi:10.1016/j.rser.2010.07.040
- Van Hoof J. Forty years of Fanger’s model of thermal comfort: Comfort for all? Indoor Air. 2008;18(3):182-201. doi:10.1111/j.1600-0668.2007.00516.x
- Boerstra AC, Kulve M te, Toftum J, Loomans MGLC, Olesen BW, Hensen JLM. Comfort and performance impact of personal control over thermal environment in summer: Results from a laboratory study. Build Environ. 2015;87:315-326. doi:10.1016/j.buildenv.2014.12.022
- Erickson VL, Cerpa AE. Thermovote: Participatory sensing for efficient building HVAC conditioning. In: BuildSys 2012 - Proceedings of the 4th ACM Workshop on Embedded Systems for Energy Efficiency in Buildings. New York, New York, USA: ACM Press; 2012:9-16. doi:10.1145/2422531.2422534