T04 Individual Thermal Control (WELL v2, Q2 2025)
Concept: Thermal Comfort · Type: Optimization · Maximum points: 3
Intent
Maximize and personalize thermal comfort among all individuals.Summary
This WELL feature requires projects to improve thermal comfort of people in the space through the provision of personal thermal comfort devices and flexible dress codes that support individual thermal preferences.
Issue
Many thermal comfort standards (such as ASHRAE 55) aim to provide a thermal environment, where at minimum 80% of people will perceive the thermal environment as acceptable.1 Due to the individualized nature of thermal comfort, not everyone will be equally comfortable under the same environmental conditions. Besides the six primary factors of thermal comfort, many secondary factors, such as age, sex, health condition, personal thermal adaptation and thermal history, including climatological origin, are considered as major secondary factors.2–5Factors, such as temperament, preferences, social and cultural norms and seasonal variation also play an important role in determining individual thermal comfort.6,7
Evidence
Adopting holistic approaches through the provision of individual thermal control devices results in improved individual thermal comfort and in the expansion of the thermal comfort acceptability limits.6,8 Individual thermal control also allows for a broader range of recommended indoor air temperatures, which is linked to energy savings potential.9–11 In larger shared spaces, use of personalized equipment is a good strategy to give people the ability to better control their sensation and comfort.12–14 For example, the use of a chair equipped with fans allows the room air temperature to increase without compromising thermal comfort.15–17 In addition, flexible dress codes are important, because clothing insulation is also one of the primary forms of intervention for addressing suboptimal thermal conditions.18
Requirements
T04.1 Provide Personal Cooling Options — 1 point
Applies to: All Spaces; excluding Dwelling Units.
The project provides all regular occupants with the ability to cool their individual environment through at least one of the following:1
A user-adjustable thermostat, which controls the environment for no more than one person and is connected to the building’s mechanical cooling system or a more localized air conditioning unit.
A desk, standing, pedestal or ceiling fan that does not increase air speed for other occupants.
Chair with mechanical cooling system.
Any other solution capable of affecting a PMV change of -0.5 within 15 minutes from activation, without changing the PMV for other occupants.
Verification: On-site Photographs, Letter of Assurance – Engineer
Photographs should showcase:
1) The mechanism occupants can use to cool themselves.
Quantity: At least four workstations per floor for 10% of all floors within the project, up to a maximum of three floors.
WELL Core:
Meet these requirements in non-leased spaces. To earn an additional point, meet these requirements in all leased spaces.
T04.2 Provide Personal Heating Options — 1 point
Applies to: All Spaces; excluding Commercial Kitchen Spaces, Dwelling Units.
The project provides all regular occupants with the ability to warm their individual environment through at least one of the following:1
A user-adjustable thermostat, which controls the environment for no more than one person and is connected to the building’s mechanical heating system.
Electric parabolic space heater.
Electric heated chair or footwarmers.
Personal or shared blankets. Shared blankets are washed or disinfected at least weekly after use.
Any other solution capable of affecting a PMV change of +0.5 within 15 minutes from activation, without changing PMV for other occupants.
Verification: On-site Photographs, Letter of Assurance – Engineer
Photographs should showcase:
1) The mechanism occupants can use to heat themselves.
Quantity: At least four workstations per floor for 10% of all floors within the project, up to a maximum of three floors.
WELL Core:
Meet these requirements in non-leased spaces. To earn an additional point, meet these requirements in all leased spaces.
T04.3 Allow Flexible Dress Code — 1 point
Applies to: All Spaces; excluding Commercial Kitchen Spaces, Dwelling Units.
The following requirement is met:
A flexible dress code policy is in place that allows regular occupants to dress for individual thermal preferences.19
Verification: Policy and/or Operations Schedule
WELL Core:
Meet these requirements for direct staff.Frequently asked questions
My project requires employees to wear uniforms; how can we accommodate the flexible dress code requirements?
Projects that require employees to wear uniforms can comply with this feature by offering different uniform options that allow employees to dress to their thermal comfort preferences such as an option to wear khaki pants or shorts / a short or long sleeve button down.
References
- American Society of Heating Refrigerating and Air-Conditioning Engineers. ASHRAE 55-2020: Thermal Environmental Conditions for Human Occupancy. 2021. https://www.techstreet.com/ashrae/standards/ashrae-55-2020?product_id=2207271.
- Ning H, Wang Z, Zhang X, Ji Y. Adaptive thermal comfort in university dormitories in the severe cold area of China. Build Environ. 2016;99:161-169. doi:10.1016/j.buildenv.2016.01.003
- Luo M, Ji W, Cao B, Ouyang Q, Zhu Y. Indoor climate and thermal physiological adaptation: Evidences from migrants with different cold indoor exposures. Build Environ. 2016;98:30-38. doi:10.1016/j.buildenv.2015.12.015
- van Hoof J, Schellen L, Soebarto V, Wong JKW, Kazak JK. Ten questions concerning thermal comfort and ageing. Build Environ. 2017;120(1):123-133. doi:10.1016/j.buildenv.2017.05.008
- Van Hoof J. Forty years of Fanger’s model of thermal comfort: Comfort for all? Indoor Air. 2008;18(3):182-201. doi:10.1111/j.1600-0668.2007.00516.x
- Nicol F, Humphreys M. Maximum temperatures in European office buildings to avoid heat discomfort. Sol Energy. 2007;81(3):295-304. doi:10.1016/j.solener.2006.07.007
- de Dear RJ, Brager GS. Developing an adaptive model of thermal comfort and preference. ASHRAE Trans. 1998;104(Pt 1A):145-167.
- Rupp RF, Vásquez NG, Lamberts R. A review of human thermal comfort in the built environment. Energy Build. 2015;105:178-205. doi:10.1016/j.enbuild.2015.07.047
- Zhang H, Arens E, Pasut W. Air temperature thresholds for indoor comfort and perceived air quality. Build Res Inf. 2011;39(2):134-144. doi:10.1080/09613218.2011.552703
- Sekhar SC. Higher space temperatures and better thermal comfort - a tropical analysis. Energy Build. 1995;23(1):63-70. doi:10.1016/0378-7788(95)00932-N
- Schiavon, S. & Melikov A. Energy saving and improved comfort by increased air movement. Energy Build. 2008;40(10):313-360. https://www.sciencedirect.com/science/article/pii/S0378778808001084.
- Pan CS, Chiang HC, Yen MC, Wang CC. Thermal comfort and energy saving of a personalized PFCU air-conditioning system. Energy Build. 2005;37(5):443-449. doi:10.1016/j.enbuild.2004.08.006
- Gao C, Kuklane K, Wang F, Holmér I. Personal cooling with phase change materials to improve thermal comfort from a heat wave perspective. Indoor Air. 2012;22(6):523-530. doi:10.1111/j.1600-0668.2012.00778.x
- Pasut W, Zhang H, Arens E, Zhai Y. Energy-efficient comfort with a heated/cooled chair: Results from human subject tests. Build Environ. 2015;84:10-21. doi:10.1016/j.buildenv.2014.10.026
- Watanabe S, Shimomura T, Miyazaki H. Thermal evaluation of a chair with fans as an individually controlled system. Build Environ. 2009;44(7):1392-1398. doi:10.1016/j.buildenv.2008.05.016
- Schiavon, S., Yang, B., Donner, Y., Chang, VW, & Nazaroff W. Thermal comfort, perceived air quality and cognitive performance when personally controlled air movement is used by tropically accllimatized persons. Indoor Air. 2016;27(3):609-702. doi:10.1111/ina.12046
- Zhang H, Arens E, Zhai Y. A review of the corrective power of personal comfort systems in non-neutral ambient environments. Build Environ. 2015;91:15-41. doi:10.1016/j.buildenv.2015.03.013
- Nicol JF, Humphreys MA. Thermal Comfort As Part of a Self-Regulating System. Build Res Pr. 1973;1(3):174-179. doi:10.1080/09613217308550237
- Health and Safety Executive. Thermal Comfort. https://www.hse.gov.uk/temperature/thermal/index.htm. Published 1999.