W03 Basic Water Management (WELL v2, Q2 2025)

Concept: Water · Type: Precondition

Intent

Implement protocols to reduce risk of water quality loss and Legionella colonization

Summary

This WELL feature requires projects to proactively test drinking water and to manage recirculating hot water systems against Legionella colonization.

Issue

All water systems require some degree of validation to ensure that the health targets are met under its operational conditions, for which sampling is an effective verification tool1. Legionella bacteria is naturally present in waters at low concentrations, but it may colonize recirculated water systems and can cause lung disease and even death if contaminated water aerosols are inhaled.2 Legionnaire’s disease affects especially the immunocompromised, smokers and those over age 50.2 Assets commonly vulnerable to Legionella infestation include domestic potable and hot water systems, cooling towers, humidifiers, misters, decorative fountains, spas and hot tubs.2  

Evidence

Basic management for water quality ensures that the water sourcing, treatment and delivery operates as designed. Turbidity, residual chlorine and pH monitoring help control basic chemical and microbiological water characteristics and, if trends are detected, may inform that actions may be needed to protect the quality of the water, such as changing a filter, check the building’s pipes for leaks or inquire with the city for major works in the area. Management for minimizing Legionella requires a thorough and quantitative risk assessment of buildings’ water assets, identifying locations where control is required, and a well-documented maintenance and operations program.3 Implementing a proper Legionella management plan should reduce the risk of exposure to pathogenic bacteria.

Requirements

W03.1 Monitor Chemical and Biological Water Quality — Precondition

Applies to: All Spaces; excluding Dwelling Units.

Drinking water quality report

The following requirements are met:

Verification: On-going Data Report

On-going testing does not need to be performed by a WELL Performance Testing Agent.

WELL Core:

Meet these requirements in non-leased spaces.

W03.2 Implement Legionella Management Plan — Precondition

Applies to: All Spaces.

Meet all of the following options:

Option 1: Legionella plan development

The project provides a Legionella management plan that meets the following requirements:

Verification: Technical Document (Audited)

Legionella management plan. Interiors projects may use building-wide Legionella management plans.

Option 2: Legionella plan implementation

The following requirement is met:

Verification: On-going Maintenance Report

WELL Core:

Meet these requirements in the whole building. 

Frequently asked questions

Does the Legionella management plan apply to projects even if no cooling towers are present?

Yes, the Legionella management plan applies to all projects even if no cooling towers are present. It is possible for a project to implement a streamlined legionella plan representative of the risk level at the project building. Other devices and spaces to consider, besides cooling towers, may include: domestic hot and cold water systems, decorative fountains, shower heads and any other source where water aerosols could be generated.

Can drinking water quality test reports from a local water source be used to meet the requirements?

No, these water quality parameters need to be tested on-site since they may change as water flows through the pipes between the treatment plant, the project's water intake, and the plumbing pipes and fixtures within the project.

Do Interiors projects need to create and implement a Legionella plan?

Yes. Interiors projects must create and implement a Legionella plan. Projects are responsible for legionella management within the project boundary, even if systems are owned and managed by a base building. It is acceptable for an interiors project to use a base building management plan to meet feature requirements as long as it also covers any relevant systems installed by the tenant.

Is water used in fire protection systems (e.g., sprinklers) within the scope of the Legionella management plan?

Yes, water used for fire protection falls under the scope of the Legionella management plan and must be considered as part of the hazard analysis. Systems with cross-connection between the fire protection system and the main potable water supply do increase Legionella growth risk, whereas systems that include backflow prevention into the main drinking water supply likely carry lower risk. Projects must assess all applicable systems and determine the appropriate level of risk. 

If my plan includes protocols for legionella sampling, is the sampling required to be conducted for initial certification?

No, Legionella sampling is not required for initial certification. If sampling was performed as prescribed in the plan before document submission, then these results should be included in the documentation.

For the Water concept, are the WELL requirements for drinking water testing applicable only to cold water?

According to the WELL Performance Verification Guidebook, sampling for water for human contact is conducted on cold water. Hot water sources such as coffee makers are out of scope. However, for mixed water faucets, the hot supply should be turned off. If water temperature conditions cannot be altered, testing is conducted using the available water.

I am unsure how to develop and implement a Legionella management plan compliant with WELL in my space, or if I even need to do so. Where can I start?

All locations that use hot water must develop and implement a Legionella management plan. The complexity of the plan, however, varies significantly with the size of the project and the level of control and influence that the project owner has over the building. You can find a 'how-to' guide to support you in scoping a Legionella management plan that is compliant with WELL requirements here.