W02 Drinking Water Quality (WELL v2, Q2 2025)
Concept: Water · Type: Precondition
Intent
Provide access to drinking water that complies with health-based limits on chemical composition.
Summary
This WELL feature requires projects to provide drinking water that meets thresholds on chemicals as published by research and regulatory organizations.Issue
The chemical composition of drinking water, and therefore, its quality, changes from city to city and even within buildings due to the highly variable conditions of its sourcing, treatment and distribution within cities and inside buildings.1 For example, natural deposits have caused arsenic to leach into some groundwaters to reach levels above drinking water health guidelines.2 Water streams can also pick up contaminants from agricultural runoffs and direct industrial discharges,3 whereas drinking water may encounter many opportunities to pick up contaminants in its travel from a treatment plant to the point of use, including corrosion byproducts such as lead and copper.1 Disinfectants used to prevent microbial growth and render water potable, such as chlorine, may react with natural organic matter and yield unwanted disinfectant byproducts (DBPs) such as trihalomethanes (THMs) and haloacetic acids (HAAs), to which chronic exposure needs to be minimized.4
Evidence
Drinking water is treated and distributed to meet applicable legal requirements and regulations that may differ by country,5 and many building-scale interventions can improve water quality depending on the contaminants that need to be removed. Typical technologies able to capture contaminants include activated carbon filters, ion exchange resins and reverse osmosis (RO) systems. Evaluating chemical parameters such as pH and free chlorine may inform of the potential for the uptake of corrosion byproducts and/or bacterial growth in drinking water.1Requirements
W02.1 Meet Chemical Thresholds — Precondition
Applies to: All Spaces.
The following requirements are met:
The project provides at least one drinking water dispenser, plus one drinking water dispenser per dwelling unit (if applicable).
Drinking water dispensers provide water that meets the following parameters:1
- Arsenic ≤ 0.01 mg/L.
- Cadmium ≤ 0.003 mg/L.
- Chromium (total) ≤ 0.05 mg/L.
- Copper ≤ 2 mg/L.
- Fluoride ≤ 1.5 mg/L.
- Lead ≤ 0.01 mg/L.
- Mercury (total) ≤ 0.006 mg/L.
- Nickel ≤ 0.07 mg/L.
- Nitrate ≤ 50 mg/L as Nitrate (11 mg/L as Nitrogen).
- Nitrite ≤ 3 mg/L as Nitrite (0.9 mg/L as Nitrogen).
- Total chlorine ≤ 5 mg/L.
Drinking water dispensers provide water that meets the following parameters:
- Residual (free) chlorine does not exceed 4 mg/L.3
- The concentration of total trihalomethanes (TTHM, sum of dibromochloromethane, bromodichloromethane, chloroform and bromoform) is 0.08 mg/L or less.3
- The concentration of haloacetic acids (HAA5, sum of chloroacetic, dichloroacetic, trichloroacetic, bromoacetic and dibromoacetic acids) is 0.06 mg/L or less.3
Multifamily residential projects may achieve WELL Certification at the Bronze or Silver level without testing in dwelling units, but cannot achieve Gold or Platinum without testing in dwelling units. See Sampling Rates for Multifamily Residential in the WELL Performance Verification Guidebook for further details.
Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.
Verification: Performance Test
Performance verification: Disinfectants
Test method:
- Take measurements of total and free chlorine of samples by adding the appropriate reagents as specified by the chlorine meter manufacturer. To calculate residual chloramines, subtract the free chlorine value from the total chlorine value.
- Repeat the process twice, for a total of three samples per water fixture tested.
Device requirements:
- Measurement range: 0-5 mg/L
- Reporting resolution: 0.01 mg/L or finer
- Accuracy: ±0.02 mg/L at 1.00 mg/L
Reporting and compliance:
- At each fixture, the average of the three samples must comply with the requirements in WELL.
Performance verification: Lead
Test method:
- Appropriate sampling vials must be obtained from the laboratory prior to performance testing.
- Follow all laboratory procedures for collecting and packaging the sample.
Reporting and compliance:
- The sample from every fixture tested must meet the requirements in WELL for lead.
Performance verification: Laboratory-based parameters (except lead)
Test method:
- Appropriate sampling vials must be obtained from the laboratory prior to performance testing.
- Follow all laboratory procedures for collecting and packaging the sample.
- Package and ship sample to third party testing laboratory per the laboratory’s instructions.
- This parameter is tested at drinking water fixtures and water fixtures used for cooking purposes for commercial kitchens (as applicable).
Reporting and compliance:
- The sample from every fixture tested must meet the requirements in WELL for each of the contaminants being tested.
- For Styrene samples, a "Not Detected" measurement with a limit of detection of .001 mg/L is considered acceptable.
WELL Core:
Meet these requirements in the whole building. Water will be sampled from non-leased spaces and the project must either:
- Confirm that the same water treatment system (if applicable) will be used in all leased spaces.
- Provide an allowance to tenants to purchase the same type of treatment system (if applicable) in leased spaces. If there is no water supply in non-leased spaces, water will be sampled from leased spaces.
W02.2 Meet Thresholds for Organics and Pesticides — Precondition
Applies to: All Spaces.
Meet any one of the following options:
Option 1: Drinking water quality report
The following requirements are met:
A municipal water quality report issued not more than one year before enrollment or the start of subscription reports on at least two of the pesticides below. All reported pesticides within the municipal water quality report comply with the following thresholds or are found to be compliant through Option 2, On-Site Testing:1
- Aldrin and Dieldrin (combined): 0.00003 mg/L or less.
- Atrazine: 0.1 mg/L or less.
- Carbofuran: 0.007 mg/L or less.
- Chlordane: 0.0002 mg/L or less.
- 2,4-Dichlorophenoxyacetic acid (2,4-D): 0.03 mg/L or less.
- Dichlorodiphenyltrichloroethane (DDT) and metabolites: 0.001 mg/L or less.
- Lindane: 0.002 mg/L or less.
- Pentachlorophenol (PCP): 0.009 mg/L or less.
A municipal water quality report issued not more than one year before enrollment or the start of subscription reports on at least three of the organic contaminants below. All reported organic contaminants within the municipal water quality report comply with the following thresholds or are found compliant through Option 2, On-Site Testing:1
- Benzene: 0.01 mg/L.
- Benzo[a]pyrene: 0.0007 mg/L.
- Carbon tetrachloride: 0.004 mg/L.
- 1,2-Dichloroethane: 0.03 mg/L.
- Tetrachloroethene (Tetrachloroethylene): 0.04 mg/L.
- Toluene: 0.7 mg/L.
- Trichloroethene: 0.02 mg/L.
- 2,4,6-Trichlorophenol: 0.2 mg/L.
- Vinyl Chloride: 0.0003 mg/L.
- Xylenes (o-, m- and p-): 0.5 mg/L.
Verification: Technical Document (Individual)
A municipal water quality report that includes a description of sample location (e.g., drinking water plant serving the facility or nearby point in the distribution system), the number of samples, the range of results (if more than one sample) and the frequency of sampling (e.g., annual, quarterly, monthly).
Option 2: On-site testing
The following requirements are met:
Testing must be conducted at drinking water dispensers for at least two of the pesticides from the list below. All contaminants in the list below that are reported by the lab must comply with the following thresholds:
- Aldrin and Dieldrin (combined): 0.00003 mg/L or less.
- Atrazine: 0.1 mg/L or less.
- Carbofuran: 0.007 mg/L or less.
- Chlordane: 0.0002 mg/L or less.
- 2,4-Dichlorophenoxyacetic acid (2,4-D): 0.03 mg/L or less.
- Dichlorodiphenyltrichloroethane (DDT) and metabolites: 0.001 mg/L or less.
- Lindane: 0.002 mg/L or less.
- Pentachlorophenol (PCP): 0.009 mg/L or less.
Testing must be conducted at drinking water dispensers for at least three of the organic contaminants from the list below. All contaminants in the list below that are reported by the lab must comply with the following thresholds:
- Benzene: 0.01 mg/L.
- Benzo[a]pyrene: 0.0007 mg/L.
- Carbon tetrachloride: 0.004 mg/L.
- 1,2-Dichloroethane: 0.03 mg/L.
- Tetrachloroethene (Tetrachloroethylene): 0.04 mg/L.
- Toluene: 0.7 mg/L.
- Trichloroethene (Trichloroethylene): 0.02 mg/L.
- 2,4,6-Trichlorophenol: 0.2 mg/L.
- Vinyl Chloride: 0.0003 mg/L.
- Xylenes (o-, m- and p-): 0.5 mg/L.
Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.
Verification: Performance Test
Performance verification: Laboratory-based parameters (except lead)
Test method:
- Appropriate sampling vials must be obtained from the laboratory prior to performance testing.
- Follow all laboratory procedures for collecting and packaging the sample.
- Package and ship sample to third party testing laboratory per the laboratory’s instructions.
- This parameter is tested at drinking water fixtures and water fixtures used for cooking purposes for commercial kitchens (as applicable).
Reporting and compliance:
- The sample from every fixture tested must meet the requirements in WELL for each of the contaminants being tested.
- For Styrene samples, a "Not Detected" measurement with a limit of detection of .001 mg/L is considered acceptable.
WELL Core:
Meet these requirements in the whole building. For Option 2, water will be sampled from non-leased spaces and the project must either:
- Confirm that the same water treatment system (if applicable) will be used in all leased spaces.
- Provide an allowance to tenants to purchase the same type of treatment system (if applicable) in leased spaces. If there is no water supply in non-leased spaces, water will be sampled from leased spaces.
Frequently asked questions
For the Water concept, are the WELL requirements for drinking water testing applicable only to cold water?
According to the WELL Performance Verification Guidebook, sampling for water for human contact is conducted on cold water. Hot water sources such as coffee makers are out of scope. However, for mixed water faucets, the hot supply should be turned off. If water temperature conditions cannot be altered, testing is conducted using the available water.
My test report contains more trihalomethanes (TTHM) than the four listed in the feature language (dibromochloromethane, bromodichloromethane, chloroform and bromoform). Should the total be all those listed in the lab report or only the sum of the four listed in the feature language?
The thresholds in the WELL feature are for the sum of the four parameters listed. If additional chemicals characterized as trihalomethanes are reported, they should not be included in this total.
My test report contains more haloacetic acids (HAAs) than the five listed in the feature language (chloroacetic, dichloroacetic, trichloroacetic, bromoacetic and dibromoacetic acids, collectively known as HAA5). Should the total be all those listed in the lab report or only the sum of the five listed in the feature language?
The thresholds in the WELL feature are for the sum of the five parameters listed. If additional chemicals characterized as Haloacetic acids are reported, they should not be included in this total.
References
- World Health Organization. Guidelines for drinking-water quality. 4th ed. Geneva, Switzerland: WHO Press; 2017.
- World Health Organization. Arsenic. http://www.who.int/news-room/fact-sheets/detail/arsenic. Published 2018. Accessed 2020.
- U.S. Environmental Protection Agency. National primary drinking water regulations. https://www.epa.gov/ground-water-and-drinking-water/national-primary-drinking-water-regulations. Published 2009. Accessed January 20, 2020.
- World Health Organization. Trihalomethanes in Drinking-water. Geneva, Switzerland2005.
- World Health Organization. Water Safety in Buildings. Geneva, 2011.