W01 Water Quality Indicators (WELL v2, Q2 2025)
Concept: Water · Type: Precondition
Intent
Verify the quality of water for human contact through easy-to-test parameters.
Summary
This WELL feature requires the provision of water that meets thresholds for turbidity and coliforms for all water likely to come in contact with building occupants and verifies performance using on-site tests.Issue
Most cities have an extensive treatment system to produce and deliver water with safety and integrity. Two parameters—total coliforms and turbidity— are commonly used to assess the effectiveness of these systems as easy-to-test measurements for the possible presence of other, more concerning contaminants, and are therefore known as ‘indicators’. Coliform bacteria are naturally present in the environment and are generally considered harmless. However, some coliforms are associated with fecal contamination and may cause disease if ingested.1 Turbidity is a measure of water cloudiness, which per-se does not constitute a health concern, however, it does relate to the availability of food and shelter for microbes, the presence of particulate contaminants and issues with the water treatment process,1 along with posing an aesthetic concern. High turbidity water also can reduce the efficacy of water treatment technologies.1Evidence
Water filtration can reduce turbidity and, depending on the type of device, may also trap bacteria and other contaminants. If the water has low turbidity, disinfection at the point of use with ultraviolet (UV) light may be effective at killing coliforms and pathogenic microbes.2
Requirements
W01.1 Verify Water Quality Indicators — Precondition
Applies to: All Spaces.
Water delivered to the project and intended for human contact (e.g., drinking, cooking and dishwashing, handwashing, showering or bathing) meets the following thresholds:
Turbidity is less than or equal to 1.0 NTU, FTU or FNU (nephelometric turbidity, formazin turbidity or formazin nephelometric units, respectively).
Coliforms are not detected in any 100 ml sample.
Multifamily residential projects may achieve WELL Certification at the Bronze or Silver level without testing in dwelling units, but cannot achieve Gold or Platinum without testing in dwelling units. See Sampling Rates for Multifamily Residential in the WELL Performance Verification Guidebook for further details.
Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.
Verification: Performance Test
Performance verification: Turbidity
Test method:
- Mix the sample to thoroughly disperse the solids. Wait until air bubbles disappear, then pour the sample into the turbidimeter tube.
- Repeat turbidity test twice, for a total of three samples at a water fixture.
Device requirements:
- Turbidimeter meets or exceeds requirements of EPA Method 180.1.
- Measurement range: 0-40 NTU or greater
- Reporting resolution: 0.02 NTU or finer
- Accuracy: ±2% of reading
- Lowest detectable limit: 0.05 NTU or lower
- Maintain device calibration in accordance with the manufacturer’s instructions.
Reporting and compliance:
- At each fixture, average the turbidity of the three samples.
- Compliance is based on the average at each fixture meeting the requirements listed in WELL.
Performance verification: Coliforms
Test method:
- Do not “flame” (sanitize) or remove aerator from faucet.
- Package and ship sample to testing laboratory per the laboratory’s instructions. Total coliforms sampling analysis is time-sensitive and the samples should be shipped overnight to the laboratory the same day they are collected, or couriered or driven to the laboratory the day they are collected.
Reporting and compliance:
- Each sample analyzed must comply with the requirement in WELL.
WELL Core:
Meet these requirements in the whole building.Frequently asked questions
For the Water concept, are the WELL requirements for drinking water testing applicable only to cold water?
According to the WELL Performance Verification Guidebook, sampling for water for human contact is conducted on cold water. Hot water sources such as coffee makers are out of scope. However, for mixed water faucets, the hot supply should be turned off. If water temperature conditions cannot be altered, testing is conducted using the available water.
Are the WELL water quality requirements applicable in bathrooms that are outside the project boundary?
Is water used for purposes other than human contact, such as urinals, flushing toilets, or irrigation required to meet any of the WELL water quality preconditions?
No, only water being used in situations that lead to human contact are required to meet the water quality requirements.Is reclaimed water (used for urinals, toilets, dishwasher, and irrigation) required to meet any of the WELL Water Quality requirements?
No, water being used in situations that do not lead to human contact are not required to meet the water quality requirements.References
- World Health Organization. Guidelines for drinking-water quality. 4th ed. Geneva, Switzerland: WHO Press; 2017.
- US Centers for Disease Control & Prevention. A Guide to Drinking Water Treatment Technologies for Household Use. https://www.cdc.gov/healthywater/drinking/home-water-treatment/household_water_treatment.html. Published 2014. Accessed Accessed December 10, 2019.