L04 Electric Light Glare Control (WELL v2, Q2 2025)
Concept: Light · Type: Optimization · Maximum points: 2
Intent
Minimize glare caused by electric light.Summary
This WELL feature requires projects to manage glare by using strategies, such as calculation of glare and choosing the appropriate light fixtures for the space.Issue
Glare is defined as excessive brightness of the light-source, excessive brightness-contrasts and excessive quantity of light1,2 and is an integral part of lighting design. Reducing glare improves the visual experience of the occupants in the space. Glare has been associated with a host of health issues that range from visual discomfort and eye fatigue to headaches and migraines.1,3 Studies have also shown that glare can lead to visual impairment and discomfort, which can cause accidents in the workplace. Individuals under the age of 50 are more sensitive to glare.4 Since a substantial section of the workforce falls into this age group, it is important to address glare to avoid visual fatigue and glare-induced headaches.
Evidence
Electric lighting, the light source, type of luminaires and lighting layout can help to reduce glare.Requirements
L04.1 Manage Glare from Electric Lighting — 2 points
Applies to: All Spaces; excluding Industrial.
Meet any one of the following options:
Option 1: Luminaire considerations
All luminaires within regularly occupied spaces (excluding wall wash fixtures, concealed fixtures, emergency lighting and decorative fixtures installed as specified by the manufacturer) meet one of the following requirements when measured at light output representative of regular use conditions:
100% of light is emitted above the horizontal plane.
Classified with Unified Glare Rating (UGR) of 19 or lower.
Luminance that does not exceed 6,000 cd/m2 at any angle between 45 and 90 degrees from nadir.
Verification: Technical Document (Audited)
Product specification sheets
Option 2: Space considerations
All regularly occupied spaces meet the following requirement:
Classified with Unified Glare Rating (UGR) of 19 or lower.
Verification: Technical Document (Audited)
Modeling report
Applies to: Industrial.
Meet any one of the following options:
Option 1: Luminaire considerations
All luminaires within regularly occupied spaces (excluding wall wash fixtures, concealed fixtures, emergency lighting and decorative fixtures installed as specified by the manufacturer) meet one of the following requirements when measured at light output representative of regular use conditions:
100% of light is emitted above the horizontal plane.
Classified with Unified Glare Rating (UGR) of 19 or lower.
Luminance that does not exceed 6,000 cd/m2 at any angle between 45 and 90 degrees from nadir.
Verification: Technical Document (Audited)
Product specification sheets
Option 2: Space considerations
All regularly occupied spaces meet the following requirement:
Unified Glare Rating (UGR) of 19 or lower.
Verification: Technical Document (Audited)
Modeling report
WELL Core:
Meet these requirements in non-leased spaces. To earn an additional point, also meet requirements in leased spaces.
WELL Core projects where non-leased space represents 40% or more of total project area may pursue the additional point without achieving the feature requirements in tenant spaces. Projects utilizing this pathway should include a note on the documentation required by the feature.
Frequently asked questions
For Part 1, can a project use a combination of strategies to comply? In other words, can they utilize the luminaire considerations option in some spaces and the space considerations option in other areas?
Yes, a combination of approaches can be used to satisfy Part 1, provided all regularly occupied spaces are addressed. For example, if a project has five regularly occupied spaces, three can utilize the luminaire considerations criteria and the other two can utilize the space considerations option. This should be clearly communicated in the documentation, so that the WELL Reviewer understands how the strategies are being implemented.
Does the requirement "100% of light is emitted above the horizontal plane" mean that all light issued from a fixture must be indirect?
In short, yes. 100% "indirect" also means 100% "uplight". All light must be emitted upwards from the horizontal plane at the height of each luminaire. This is beneficial for managing glare because fixtures with 100% uplight, when viewed below, have no visible luminous aperture.
My project contains repetitive space configurations. Do they all need to be modeled for compliance with Option 2?
Only unique configurations of a space need to be modeled. For example, if multiple spaces have the same geometry, furnishings, finishes, and light fixtures, only one space needs to be modeled to demosntrate compliance. If applying a single plan to demonstrate compliance for multiple similar spaces, ensure the plans are annotated to confirm that all represented floors have the same conditions.
References
- Mainster MA, Turner PL. Glare’s causes, consequences, and clinical challenges after a century of ophthalmic study. Am J Ophthalmol. 2012;153(4):587-593. doi:10.1016/j.ajo.2012.01.008
- Abrahamsson M, Sjostrand J. Impairment of contrast sensitivity function (CSF) as a measure of disability glare. Investig Ophthalmol Vis Sci. 1986;27(7):1131-1136.
- Harle DE, Shepherd AJ, Evans BJW. Visual stimuli are common triggers of migraine and are associated with pattern glare. Headache. 2006;46(9):1431-1440. doi:10.1111/j.1526-4610.2006.00585.x
- Wolska A, Sawicki D. Evaluation of discomfort glare in the 50+ elderly: Experimental study. Int J Occup Med Environ Health. 2014;27(3):444-459. doi:10.2478/s13382-014-0257-9