L03 Circadian Lighting Design (WELL v2, Q2 2025)
Concept: Light · Type: Optimization · Maximum points: 3
Intent
Support circadian and psychological health through indoor daylight exposure and outdoor views.Summary
This WELL feature requires projects to provide users with appropriate exposure to light for maintaining circadian health and aligning the circadian rhythm with the day-night cycle.Issue
Our body’s circadian rhythms are kept in sync by various cues, including light. Humans have evolved to base their circadian rhythms around the natural light-dark patterns associated with daytime and night-time. However, with humans being indoors for extended periods of time, exposure to adequate levels of light have been compromised as typical indoor electric light levels often do not equate to the amount of light the human body traditionally receives outdoors.1 Light deficiencies affects the functioning of the circadian system and quality of sleep. Disruption of circadian rhythm has been linked with obesity, diabetes, depression and metabolic disorders.2–4 Exposure to light at night has also been associated with negative health effects, such as breast cancer, circadian phase disruption and sleep disorders.5,6
Evidence
Since circadian response of humans to light is dependent on the light that enters the eye, factors such as spectral properties of the light, brightness levels, duration, and timing of exposure should be considered. The light levels must be achieved on the vertical plane, at the eye level of the occupant to simulate the light entering the eye of the user.7,8 It is also important to consider the duration of exposure to light, as well as the timing of exposure. Stimulating the circadian system at night through exposure to bright light can negatively impact sleep quality.5,9,10
Requirements
L03.1 Meet Lighting for Day-Active People — 1–3 points (max 3)
Applies to: All Spaces; excluding Dwelling Units, Guest Rooms.
For workstations used during the daytime, electric lighting is used to achieve the following thresholds:
The following light levels are achieved for at least four hours (beginning by noon at the latest) at a height of {{well-unit}}18 in|45 cm{{/well-unit}} above the work-plane for all workstations in regularly occupied spaces:
Tier Threshold Threshold for Projects with Enhanced Daylight Points 1 At least 150 EML [136 melanopic EDI] OR At least 120 EML [109 melanopic EDI] and either L05 Part 1 or L06 Part 1 {{well-points}} 1|2 {{/well-points}}
2 At least 275 EML [250 melanopic EDI]11 OR At least 180 EML [163 melanopic EDI] and either L05 Part 1 or L06 Part 1 {{well-points}} 3|4{{/well-points}}
The light levels are achieved on the vertical plane at eye level to simulate the light entering the eye of the occupant.
Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.
Verification: Performance Test
Performance verification: Circadian Lighting
Test method:
- Measurements must be recorded on a vertical plane (perpendicular to the floor) to simulate the light entering the eye of the occupant.
- The measuring instrument must be mounted on a tripod and placed on a stable surface for each measurement.
- Ensure that the shadow of the WELL Performance Testing Agent does not fall on the measuring instrument as the measurements are taken.
Device requirements:
-
All measurements are to be conducted with a cosine
corrected optical spectrometer.
- The instrument must function within the limits of the performance specifications in the below requirements when operated in accordance with the operation manual:
- Wavelength range: 380-780 nm
- Maximum acceptable overall error: ±5%
- Optical Resolution: 10 nm or less
- Range: 5-50,000 lux
- Resolution: 1 lux (at values up to 2000 lux)
- The meter is calibrated as per manufacturer specifications in an ISO/IEC 17025 Accredited Calibration Lab, or calibration must be traceable to a National Metrological Institute, such as NIST, NPL or PTB.traceable to a National Metrological Institute, such as NIST, NPL or PTB.
Reporting and compliance:
- Report the lux levels and the spectral power at 5 nm increments from 380 nm to 730 nm. The methodology described in Appendix L1 (EML = lux × melanopic ratio) will be used to calculate the equivalent melanopic lux using the recorded spectral power values.
- The median light levels must meet the EML threshold and the lowest value must be at least half the threshold.
- A tolerance of -5% EML may be considered for the measurements taken.
Applies to: Dwelling Units, Guest Rooms.
The following requirements are met in each dwelling unit:
Electric lighting is used to achieve the following light levels:
Tier Threshold Threshold for Projects with Enhanced Daylight Points 1 At least 150 EML [136 melanopic EDI] OR At least 120 EML [109 melanopic EDI] and either L05 Part 1 or L06 Part 1 1 2 At least 275 EML [250 melanopic EDI]11 OR At least 180 EML [136 melanopic EDI] and either L05 Part 1 or L06 Part 1 3 The light levels are dimmable. If automated lighting is used, it is automatically dimmed after 8:00 pm.
The light levels are achieved in living rooms and kitchens at a height of {{well-unit}}55 in|140 cm{{/well-unit}} in the center of the room. For studio apartments and guestrooms without living rooms, also test in the center of the room. If workstations are present, light levels are achieved at a height of {{well-unit}}18 in|45 cm{{/well-unit}} above the work-plane.
Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.
Verification: Performance Test
WELL Core:
Meet these requirements in the whole building. Projects must have access to at least 10% of leased space for testing (as identified by the project).
Frequently asked questions
Where are measurements taken for Circadian Lighting?
During Performance Verification, the Performance Testing Agent will take measurements at eye level to simulate the light entering the eye of the occupant. Thus, the measurement is carried out on an imaginary vertical surface located 18 inches above the horizontal workplane, and not the surface in front of occupants. If the horizontal workplane is located 30 inches above the floor (i.e. a desk), the measurements will be taken 48 inches above the floor. If the horizontal workplane is a standing desk, the measurement will be taken 18 inches above the horizontal workplane.How do photopic lux and melanopic lux differ?
Photopic lux measures irradiance weighted to the visual system (specifically, the M and L cones), known as illuminance. Equivalent melanopic measures the irradiance, weighted to the response of the the ipRGCs, which are located in the retina of the eye and are the primary driver for the circadian rhythm.Does a project team need to purchase circadian lighting technology, such as tunable white lights, to achieve this feature?
No, the EML requirements can be achieved through commonly used lighting systems, as long as lux and melanopic ratios are calculated to achieve L03 EML requirements.Can project teams achieve the circadian lighting requirements of Feature L03: Circadian Lighting Design by providing task lights to employees upon request?
Yes, projects may achieve the EML threshold through a combination of ambient lighting and task lights. If this strategy is pursued, the project is required to achieve L09: Occupant Lighting Control, Part 2: Provide Supplemental Lighting.
References
- Figueiro MG. Disruption of Circadian Rhythms by Light During Day and Night. Curr Sleep Med Reports. 2017;3(2):76-84. doi:10.1007/s40675-017-0069-0
- Cho Y, Ryu S-H, Lee BR, Kim KH, Lee E, Choi J. Effects of artificial light at night on human health: A literature review of observational and experimental studies applied to exposure assessment. Chronobiol Int. 2015;32(9):1294-1310. doi:10.3109/07420528.2015.1073158
- Li Q, Zheng T, Holford TR, Boyle P, Zhang Y, Dai M. Light at night and breast cancer risk: results from a population based case control study in Connecticut, USA. 2010;21(12):2281-2285. doi:10.1007/s10552-010-9653-z
- Kim YJ, Lee E, Lee HS, Kim M, Park MS. High prevalence of breast cancer in light polluted areas in urban and rural regions of South Korea: An ecologic study on the treatment prevalence of female cancers based on National Health Insurance data. Chronobiol Int. 2015;32(5):657-667. doi:10.3109/07420528.2015.1032413
- Legates TA, Fernandez DC, Hattar S. Light as a central modulator of circadian rhythms, sleep and affect. Nat Rev Neurosci. 2014;15(7):443-454. doi:10.1038/nrn3743
- Hurley S, Goldberg D, Nelson D, et al. Light at night and breast cancer risk among california teachers. Epidemiology. 2014;25(5):697-706. doi:10.1097/EDE.0000000000000137
- Lockley SW, Arendt J, Skene DJ. Visual impairment and circadian rhythm disorders. Dialogues Clin Neurosci. 2007;9(3):301-314. doi:10.1080/10481881209348680
- British Standards Institution. PD CEN/TR 16791:2017: Quantifying irradiance for eye-mediated non-image-forming effects of light in humans. 2017. https://shop.bsigroup.com/ProductDetail/?pid=000000000030310356.
- Koo YS, Song JY, Joo EY, et al. Outdoor artificial light at night, obesity, and sleep health: Cross-sectional analysis in the KoGES study. Chronobiol Int. 2016;33(3):301-314. doi:10.3109/07420528.2016.1143480
- Ostrin LA, Abbott KS, Queener HM. Attenuation of short wavelengths alters sleep and the ipRGC pupil response. Ophthalmic Physiol Opt. 2017;37(4):440-450. doi:10.1111/opo.12385
- Brown, T.; Brainard, G.; Cajochen, C.; Czeisler, C.; Hanifin, J.; Lockley, S.; Lucas, R.; Munch, M.; O'Hagan, J.; Peirson, S.; Price, L.; Roenneberg, T.; Schlangen, L.; Skene, D.; Spitschan, M.; Vetter, C.; Zee, P.; Wright Jr., K. Recommendations for Healthy Daytime, Evening, and Night-Time Indoor Light Exposure. Preprints 2020, 2020120037 (doi: 10.20944/preprints202012.0037.v1)