L02 Visual Lighting Design (WELL v2, Q2 2025)

Concept: Light · Type: Precondition

Intent

Provide visual comfort and enhance visual acuity for all users through electric lighting.

Summary

This WELL feature requires projects to provide appropriate illuminances on work planes for regular users of all age groups, as required for the tasks performed in the space.

Issue

Humans perceive the world through visual cues that are received through images formed on the retina of the eye. The light levels in a space can enhance the user’s ability to perform tasks in that space, while contributing to the feeling of spaciousness. The age of the individual is also a factor in the amount of light required for visual acuity. As humans age, the transmission of light through their lenses is reduced. This is due to age-related changes, including increased light absorption by the lenses, smaller pupil size, increased scattering of light due to thicker lenses and yellowing of the lenses.1,2 This aging of the eye indicates that an increase in light levels is required to ensure visual acuity.

Evidence

While developing a lighting strategy to accommodate the visual acuity of users, it is critical to take into account the tasks conducted, as well as the age of the users. Projects may refer to published recommendations by lighting associations or authorities on using electric lighting design strategies for light levels required on the work plane. Lighting recommendations published by authorities provide a range of lighting levels for different age groups and tasks.

Requirements

L02.1 Provide Visual Acuity — Precondition

Applies to: All Spaces; excluding Dwelling Units.

Meet any one of the following options:

Option 1: Visual lighting design

The following requirements are met:

Verification: Performance Test, Technical Document (Individual)

Technical Document: Design specifications that list the following:

AND

Technical Document: Architectural drawings that identify the tasks considered in each room.

Performance verification: Visual Lighting

Test method:

Device requirements:

Reporting and compliance:

Option 2: Predetermined light levels

The following requirements are met:

Verification: Performance Test, Technical Document (Individual)

Technical Document: Architectural drawings that identifies the tasks considered in each room.

Applies to: Dwelling Units.

Promote Visual Acuity

The following requirements are met:

Verification: Performance Test, Technical Document (Individual)

Technical Document: Design specifications that contain the following:

AND 

Technical Document: Architectural drawings that contain the following: Spaces where lighting is installed and spaces where lighting is not installed For spaces where lighting is not installed, specifications, quantity and location of light fixtures

AND

Technical Document: Architectural drawings that identify the tasks considered in each room.

Multifamily residential projects may achieve WELL Certification at the Bronze or Silver level without testing in dwelling units, but cannot achieve Gold or Platinum without testing in dwelling units. See Sampling Rates for Multifamily Residential in the WELL Performance Verification Guidebook for further details. 

Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.

WELL Core:

Meet these requirements in non-leased spaces. To earn an additional point, also meet these requirements in leased spaces, which requires access to at least 10% of leased space for testing (identified by the project).

Frequently asked questions

Does this feature apply to non-regularly occupied spaces?

Yes. If pursuing Option 1: Visual Lighting Design, all indoor and outdoor spaces within the project boundary, including regularly occupied spaces and non-regularly occupied spaces, are in scope. If pursuing Option 2: Predetermined Light Levels, only the listed space types, which include regularly occupied spaces and non-regularly occupied spaces, are in scope. 

What if the lighting reference guideline I've chosen doesn't include specific illuminance thresholds for all tasks in the project?

If the team's chosen lighting reference guideline doesn't include a specific illuminance threshold for a certain task, the team can identify a similar task for which a threshold does exist to use instead. Alternatively, if the team would like to use two or more lighting reference guidelines that do include a specific illuminance threshold for each task, submit an alternative adherence path (AAP) proposal that explains why more than one reference guideline is needed.

How is illuminance compliance determined?

As described in the Performance Verification Guidebook, the average illuminance for each task type / space type must meet the target thresholds identified by the project team.

References

  1. Pokorny J, Smith VC, Lutze M. Aging of the human lens. Appl Opt. 1987;26(8):1437. doi:10.1364/AO.26.001437
  2. Owsley C. Aging and vision. Vision Res. 2011;51(13):1610-1622. doi:10.1016/j.visres.2010.10.020
  3. Illuminating Engineering Society. 2020. IES OL-IM-03: Lighting Applications Standards Collection Subscription. https://store.ies.org/product/lighting-applications-standards-collection-subscription/?v=7516fd43adaa
  4. European Committee for Standardization. 2021. EN 12464-1:2021. Light and lighting - Lighting of work places - Part 1: Indoor work places. Accessed Febraury February 13, 2024. https://standards.iteh.ai/catalog/standards/sist/b1a68cbc-1bdc-4ac2-89e7-0123982763b5/sist-en-12464-2-2014
  5. European Committee for Standardization. 2014. SIST EN 12464-2:2014 Light and lighting - Lighting of work places - Part 2: Outdoor work places. Accessed Febraury February 13, 2024. https://standards.iteh.ai/catalog/standards/sist/b1a68cbc-1bdc-4ac2-89e7-0123982763b5/sist-en-12464-2-2014
  6. International Organization for Standardization. ISO 8995-1:2002 (CIE S 008/E:2001) - Lighting of work places -- Part 1: Indoor. 2001. https://www.iso.org/standard/28857.html.
  7. Zheng W. GB 50034-2013 Standard for lighting design of buildings (English Version). https://books.google.com/books/about/GB_50034_2013_Translated_English_of_Chin.html?id=svamDgAAQBAJ. Published 2013. Accessed April 1, 2018.
  8. The SLL Lighting Handbook The Society of Light and Lighting. CIBSE; 2018. www.cibse.org. Accessed June 9, 2020.
  9. U.S. General Services Administration. P100 Facilities Standards for the Public Buildings Service.; 2018. https://www.gsa.gov/cdnstatic/2018 P100 Final 5-7-19_0.pdf.