L02 Visual Lighting Design (WELL v2, Q2 2025)
Concept: Light · Type: Precondition
Intent
Provide visual comfort and enhance visual acuity for all users through electric lighting.
Summary
This WELL feature requires projects to provide appropriate illuminances on work planes for regular users of all age groups, as required for the tasks performed in the space.
Issue
Humans perceive the world through visual cues that are received through images formed on the retina of the eye. The light levels in a space can enhance the user’s ability to perform tasks in that space, while contributing to the feeling of spaciousness. The age of the individual is also a factor in the amount of light required for visual acuity. As humans age, the transmission of light through their lenses is reduced. This is due to age-related changes, including increased light absorption by the lenses, smaller pupil size, increased scattering of light due to thicker lenses and yellowing of the lenses.1,2 This aging of the eye indicates that an increase in light levels is required to ensure visual acuity.
Evidence
While developing a lighting strategy to accommodate the visual acuity of users, it is critical to take into account the tasks conducted, as well as the age of the users. Projects may refer to published recommendations by lighting associations or authorities on using electric lighting design strategies for light levels required on the work plane. Lighting recommendations published by authorities provide a range of lighting levels for different age groups and tasks.
Requirements
L02.1 Provide Visual Acuity — Precondition
Applies to: All Spaces; excluding Dwelling Units.
Meet any one of the following options:
Option 1: Visual lighting design
The following requirements are met:
All indoor and outdoor spaces (including transition areas) comply with the illuminance thresholds specified in one of the following lighting reference guidelines:
- IES Lighting Library, Lighting Applications Standards Collection.3
- EN 12464-1:20214 or EN 12464-2:2014.5
- ISO 8995-1:2002(E) (CIE S 008/E:2001).6
- GB50034-2013.7
- CIBSE SLL Code for Lighting.8
The illuminance thresholds take into consideration the tasks and the age groups of the occupants.
Verification: Performance Test, Technical Document (Individual)
Technical Document: Design specifications that list the following:
- Lighting reference guideline used.
- Tasks or activities considered for visual lighting design in the project. All tasks and activities regularly undertaken by occupants are considered.
- Illuminance criteria met for each task considered. If occupants with multiple ages ranges are present, the illuminance criteria for the oldest range may be considered.
- Height of work plane or other target of illumination ranges for the majority of occupants.
AND
Technical Document: Architectural drawings that identify the tasks considered in each room.
Performance verification: Visual Lighting
Test method:
- The measuring instrument is placed in the center of the flat surface of the working plane with the aperture facing upward.
- Ensure that the shadow of the WELL Performance Testing Agent does not fall on the measuring instrument while the measurements are taken.
Device requirements:
- All illuminance measurements are to be conducted with a cosine corrected illuminance meter.
- Range: 5-50,000 lux
- Maximum acceptable overall error: ±5% (at values up to 2000 lux)
- Resolution: 1 lux (at values up to 2000 lux)
- The illuminance meter is calibrated as per manufacturer specifications in an ISO/IEC 17025:2017 Accredited Calibration Lab, or calibration must be traceable to a National Metrological Institute, such as NIST, NPL or PTB.traceable to a National Metrological Institute, such as NIST, NPL or PTB.
Reporting and compliance:
- The average light levels across a given task must meet the target illuminance throughout the project boundary.
- The lowest light level measured across a given task must be at least half of the target illuminance.
Option 2: Predetermined light levels
The following requirements are met:
More than 50% of the occupants are under the age of 65.
The area of outdoor space within the project boundary is less than 5% of the interior project area.
At least 90% of the interior project area is comprised of the following space types and meets the associated illuminance thresholds:
Room Types Minimum Illuminance Threshold Offices
Classrooms
{{well-unit}}30 fc|320 lux{{/well-unit}} at task surface.9
Circulation areas (including lobbies and atria)
Storage spaces
{{well-unit}}10 fc|110 lux{{/well-unit}} at floor level.9 Dining areas
Lounges
Restrooms
{{well-unit}}10 fc|110 lux{{/well-unit}} at task surface.9
Verification: Performance Test, Technical Document (Individual)
Technical Document: Architectural drawings that identifies the tasks considered in each room.
Applies to: Dwelling Units.
Promote Visual Acuity
The following requirements are met:
Lighting is installed in kitchens and bathrooms to comply with the illuminance thresholds specified in one of the following lighting reference guidelines:
- IES Lighting Library, Lighting Applications Standards Collection.3
- ISO 8995-1:2002(E) (CIE S 008/E:2001).6
- GB50034-2013.7
- CIBSE SLL Code for Lighting.8
For spaces where lighting is not installed, the following is provided to all tenants:
- Illuminance thresholds for common tasks conducted in spaces
- Specifications, quantity and location of light fixtures required to meet light levels based on sample layout
Verification: Performance Test, Technical Document (Individual)
Technical Document: Design specifications that contain the following:
- Lighting reference guideline used
- Tasks or activities considered for visual lighting design in the project
- All tasks and activities regularly undertaken by occupants are considered
- Illuminance criteria met for each task considered. If occupants within multiple age ranges are present, the illuminance criteria for the oldest range may be considered
- Height of work plane or other target of illumination ranges for the majority of occupants
AND
Technical Document: Architectural drawings that contain the following: Spaces where lighting is installed and spaces where lighting is not installed For spaces where lighting is not installed, specifications, quantity and location of light fixtures
AND
Technical Document: Architectural drawings that identify the tasks considered in each room.
Multifamily residential projects may achieve WELL Certification at the Bronze or Silver level without testing in dwelling units, but cannot achieve Gold or Platinum without testing in dwelling units. See Sampling Rates for Multifamily Residential in the WELL Performance Verification Guidebook for further details.
Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.
WELL Core:
Meet these requirements in non-leased spaces. To earn an additional point, also meet these requirements in leased spaces, which requires access to at least 10% of leased space for testing (identified by the project).Frequently asked questions
Does this feature apply to non-regularly occupied spaces?
Yes. If pursuing Option 1: Visual Lighting Design, all indoor and outdoor spaces within the project boundary, including regularly occupied spaces and non-regularly occupied spaces, are in scope. If pursuing Option 2: Predetermined Light Levels, only the listed space types, which include regularly occupied spaces and non-regularly occupied spaces, are in scope.
What if the lighting reference guideline I've chosen doesn't include specific illuminance thresholds for all tasks in the project?
If the team's chosen lighting reference guideline doesn't include a specific illuminance threshold for a certain task, the team can identify a similar task for which a threshold does exist to use instead. Alternatively, if the team would like to use two or more lighting reference guidelines that do include a specific illuminance threshold for each task, submit an alternative adherence path (AAP) proposal that explains why more than one reference guideline is needed.
How is illuminance compliance determined?
As described in the Performance Verification Guidebook, the average illuminance for each task type / space type must meet the target thresholds identified by the project team.
References
- Pokorny J, Smith VC, Lutze M. Aging of the human lens. Appl Opt. 1987;26(8):1437. doi:10.1364/AO.26.001437
- Owsley C. Aging and vision. Vision Res. 2011;51(13):1610-1622. doi:10.1016/j.visres.2010.10.020
- Illuminating Engineering Society. 2020. IES OL-IM-03: Lighting Applications Standards Collection Subscription. https://store.ies.org/product/lighting-applications-standards-collection-subscription/?v=7516fd43adaa
- European Committee for Standardization. 2021. EN 12464-1:2021. Light and lighting - Lighting of work places - Part 1: Indoor work places. Accessed Febraury February 13, 2024. https://standards.iteh.ai/catalog/standards/sist/b1a68cbc-1bdc-4ac2-89e7-0123982763b5/sist-en-12464-2-2014
- European Committee for Standardization. 2014. SIST EN 12464-2:2014 Light and lighting - Lighting of work places - Part 2: Outdoor work places. Accessed Febraury February 13, 2024. https://standards.iteh.ai/catalog/standards/sist/b1a68cbc-1bdc-4ac2-89e7-0123982763b5/sist-en-12464-2-2014
- International Organization for Standardization. ISO 8995-1:2002 (CIE S 008/E:2001) - Lighting of work places -- Part 1: Indoor. 2001. https://www.iso.org/standard/28857.html.
- Zheng W. GB 50034-2013 Standard for lighting design of buildings (English Version). https://books.google.com/books/about/GB_50034_2013_Translated_English_of_Chin.html?id=svamDgAAQBAJ. Published 2013. Accessed April 1, 2018.
- The SLL Lighting Handbook The Society of Light and Lighting. CIBSE; 2018. www.cibse.org. Accessed June 9, 2020.
- U.S. General Services Administration. P100 Facilities Standards for the Public Buildings Service.; 2018. https://www.gsa.gov/cdnstatic/2018 P100 Final 5-7-19_0.pdf.