L01 Light Exposure (WELL v2, Q2 2025)
Concept: Light · Type: Precondition
Intent
Provide indoor light exposure through daylight and electric light strategies.
Summary
This WELL feature requires projects to provide appropriate light exposure in indoor environments through lighting strategies.
Issue
Mammals function on an approximately 24-hour cycle, following what are referred to as circadian rhythms.1 Light is the main driver of the circadian system, which controls body processes, such as digestion, the release of certain hormones, body temperature and sleep. Humans evolved their sleep schedules to be dependent on the natural day- night cycle. Electric light has only been widely used as a source of light for less than 200 years.2 The increase in the use of electric lighting has led to indoor environments relying on electric light over daylight. However, reduced exposure to light has been linked to the onset of depression and impairment of cognitive function in individuals.3,4 Irregular sleep-wake cycles have been linked to poorer academic performance in college students.5 Studies have shown that light exposure during daytime has been linked to increases in productivity and sleep quality, as well as reduction in symptoms of depression in individuals.6-8
Evidence
Providing indoor access to adequate light can positively influence the productivity and mood of individuals, while supporting the alignment of their circadian rhythms with the natural day-night cycle.9–12 Access to appropriate levels of light in indoor environments can be achieved through building design, façade design, space layout and lighting design. Windows, atriums and skylights are design features that can be utilized to increase daylight in a space. The interior layout of the space also has an impact on the daylight exposure received by users. For example, conference rooms can be added to the center of the floor plate, so that workstations can be situated near windows and have daylight exposure. Lighting strategies using electric lighting can be utilized to achieve required light exposure, when appropriate daylight exposure is not available.
Requirements
L01.1 Provide Indoor Light — Precondition
Applies to: All Spaces; excluding Dwelling Units, Guest Rooms.
Meet any one of the following options:
Option 1: Daylight simulation
The project demonstrates, through computer simulations, that one of the following conditions are achieved:
The total floor area of regularly occupied spaces achieves one of the following targets:
Calculations per IES LM-83 13 Calculations per Annex A of CEN 17037 sDA150,50% > 30% OR Target illuminance {{well-unit}}19 fc|200 lux{{/well-unit}} is achieved for >30% of floor area throughout 50% of daylit hours of the year Common space that has unassigned seating for at least 15% of regular occupants at any given time achieves one of the following targets:
Calculations per IES LM-83 Calculations per Annex A of CEN 17037 sDA 300,50% > 75% OR Target illuminance {{well-unit}}28 fc|300 lux{{/well-unit}} is achieved for >30% of floor area and average illuminance {{well-unit}}9 fc|100 lux{{/well-unit}} is achieved for >95% of floor area throughout 50% of daylit hours of the year
Verification: Technical Document (Audited)
Modeling report
Option 2: Interior layout
One of the following requirements is met:
At least 30% of the regularly occupied area is within a {{well-unit}}20 ft|6 m{{/well-unit}} horizontal distance of envelope glazing.
Common spaces have unassigned seating and can accommodate at least 15% of regular occupants at any given time. At least 70% of all seating in the spaces is within a {{well-unit}}16 ft|5 m{{/well-unit}} horizontal distance of envelope glazing.
Verification: Technical Document (Audited)
Architectural drawingsOption 3: Building design
One of the following requirements is met:
The envelope glazing area is no less than 7% of the regularly occupied floor area.
The floor plate is no more than {{well-unit}}65 ft|20 m{{/well-unit}} between opposite walls that each have envelope glazing, and there are no opaque obstructions higher than {{well-unit}}4 ft|1.22 m{{/well-unit}} within a {{well-unit}}20 ft|6 m{{/well-unit}} horizontal distance of the envelope glazing.
Verification: Technical Document (Audited)
Architectural drawings
Option 4: Circadian lighting design
The following requirement is met:
The project meets the threshold of Tier 1 of Feature L03: Circadian Lighting Design.
Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.
Verification: Performance Test
Applies to: Dwelling Units, Guest Rooms.
Meet any one of the following options:
Option 1: Daylight simulation
The project demonstrates, through computer simulations, that the following requirement is achieved:The total floor area of regularly occupied spaces of each dwelling unit achieves one of the following targets:
Calculations per IES LM-83 13 Calculations per Annex A of CEN 17037
sDA150,50% > 30%OR Target illuminance {{well-unit}}19 fc|200 lux{{/well-unit}} is achieved for >30% of individual unit area throughout 50% of daylit hours of the year
Verification: Technical Document (Audited)
Modeling reportOption 2: Facade design
The following requirement is met:
The envelope glazing area is no less than 7% of the regularly occupied floor area for each dwelling unit.
Verification: Technical Document (Audited)
Architectural drawings
Option 3: Circadian lighting design
The following requirement is met:The project achieves at least one point in Feature L03: Circadian Lighting Design.
Verification: Performance Test
WELL Core:
Meet these requirements in the whole building. Projects pursuing Feature L03, Option 4 to achieve this feature are required to have access to at least 10% of leased spaces for testing (identified by the project). Projects pursuing daylighting options are required to meet the requirements in each floor or for each tenant, whichever is smaller. If finishes have not finalized, projects may use the following default surface reflectances:
- Ceilings: 80%
- Floors: 20%
- Walls: 50%
If the layout of leased spaces is not yet known, the entire leased space is to be considered regularly occupied.
Frequently asked questions
Can a project team apply different options within L01 across different floors of the project?
Yes, a project team can use different options for different floors by submitting an Alternative Adherence Path (AAP) specifying which option is being used for which floor.
If a team would like to use different options and one of the options that will be pursued is Option 4: Circadian lighting design, the team will need to conduct performance testing for the floor(s) using Option 4. If the team is already targeting Feature L03, no separate performance tests are required to meet Option 4 of Feature L01. Option 4 cannot be applied to a floor with no workstations.
Can a combination of spaces be used to meet the common area seating requirements, or does a single space need to contain the seating?
Yes, a combination of spaces is acceptable, so long as combined they can seat 15% of regular occupants and each space is accessible to all occupants.
When calculating sDA and ASE in daylight modeling, can you clarify if the interior and exterior shades/blinds can be modeled for analysis?
The exterior shades/blinds should be modeled for analysis in accordance with IES LM-83 which defines the calculation of Spatial Daylight Autonomy (sDA) and Annual Sunlight Exposure (ASE).
Interior glare control (shades/blinds) should not be used for the ASE analysis, per the methodology outlined in IES LM-83, Section 3.2.6, but are allowed for the sDA analysis.
References
- Czeisler CA, Gooley JJ. Sleep and circadian rhythms in humans. Cold Spring Harb Symp Quant Biol. 2007;72:579-597. doi:10.1101/sqb.2007.72.064
- U.S. Department of Energy. The History of the Light Bulb. https://www.energy.gov/articles/history-light-bulb. Published 2013. Accessed April 1, 2018.
- Kent ST, McClure LA, Crosson WL, Arnett DK, Wadley VG, Sathiakumar N. Effect of sunlight exposure on cognitive function among depressed and non-depressed participants: A REGARDS cross-sectional study. Environ Heal A Glob Access Sci Source. 2009;8(1):34. doi:10.1186/1476-069X-8-34
- Ruger M. Time-of-day-dependent effects of bright light exposure on human psychophysiology: comparison of daytime and nighttime exposure. AJP Regul Integr Comp Physiol. 2005;290(5):R1413-R1420. doi:10.1152/ajpregu.00121.2005
- Phillips AJK, Clerx WM, O’Brien CS, et al. Irregular sleep/wake patterns are associated with poorer academic performance and delayed circadian and sleep/wake timing. Sci Rep. 2017;7(1):3216. doi:10.1038/s41598-017-03171-4
- Lam RW, Levitt AJ, Levitan RD, et al. Efficacy of bright light treatment, fluoxetine, and the combination in patients with nonseasonal major depressive disorder a randomized clinical trial. JAMA Psychiatry. 2016;73(1):56-63. doi:10.1001/jamapsychiatry.2015.2235
- Figueiro MG, Steverson B, Heerwagen J, et al. The impact of daytime light exposures on sleep and mood in office workers. Sleep Heal. 2017;3(3):204-215. doi:10.1016/j.sleh.2017.03.005
- Boubekri M, Cheung IN, Reid KJ, Wang CH, Zee PC. Impact of windows and daylight exposure on overall health and sleep quality of office workers: A case-control pilot study. J Clin Sleep Med. 2014;10(6):603-611. doi:10.5664/jcsm.3780
- Phipps-Nelson J, Redman JR, Dijk DJ, Rajaratnam SMW. Daytime exposure to bright light, as compared to dim light, decreases sleepiness and improves psychomotor vigilance performance. Sleep. 2003;26(6):695-700. doi:10.1093/sleep/26.6.695
- Legates TA, Fernandez DC, Hattar S. Light as a central modulator of circadian rhythms, sleep and affect. Nat Rev Neurosci. 2014;15(7):443-454. doi:10.1038/nrn3743
- Edwards L, Torcellini P. A Literature Review of the Effects of Natural Light on Building Occupants A Literature Review of the Effects of Natural Light on Building Occupants. Contract. 2002;(July). doi:10.2172/15000841
- Galasiu AD, Veitch JA. Occupant preferences and satisfaction with the luminous environment and control systems in daylit offices: a literature review. Energy Build. 2006;38(7):728-742. doi:10.1016/j.enbuild.2006.03.001
-
Illuminating Engineering Society. 2023. IES LM-83-23: Approved Method IES Spatial Daylight Autonomy (sDA) and Annual Sunlight Exposure (ASE). https://store.ies.org/product/approved-method-ies-spatial-daylight-autonomy-sda-and-annual-sunlight-exposure-ase/?v=0b3b97fa6688