WELL v2, Q2 2025 — this page reflects the WELL v2, Q2 2025 addenda of the WELL Building Standard.

Official source: https://v2.wellcertified.com/en/wellv2/sound/feature/7

S07 β Impact Noise Management (WELL v2, Q2 2025)

Concept: Sound · Type: Optimization · Maximum points: 3

Intent

Reduce the level of impact noise radiation by designing resilient floors.

Summary

This WELL feature requires projects to manage background noise levels by demonstrating compliance with impact noise mitigation techniques.

Issue

Sound can transmit between rooms within a building as structure-borne impact noise. This impact noise travels through structures (e.g., walls, floors, columns, piping) as vibrations that are then radiated as airborne noise to a listener.1 Impact noise typically derives from objects impacting a floor (e.g., footfall, machinery, gym equipment) and can result in workplace distractions, sleep disturbance or disrupted focus.2,3

Evidence

The overall construction of a building influences impact noise radiation levels. For example, a building that utilizes a light-weight floor construction (e.g., wood truss, cross-laminated timber, steel frame) generally exhibits higher degrees of impact noise radiation between floors.4–7 Conversely, buildings constructed with resilient, composite floor-ceiling construction (e.g., thick concrete slab, suspended ceiling, floor with an underlayment) generally exhibit lower degrees of impact noise radiation. The performance of floor-ceiling materials can be measured using the following metrics: Impact Insulation Class Rating (IIC), Normalized Impact Sound Rating (NISR) or Weighted Standardized Impact Sound Pressure Level (LnTw).

Requirements

S07.1 Specify Impact Noise Reducing Flooring — 1 point

Applies to: All Spaces.

The following requirements are met:

Verification: Technical Document (Audited), Beta Feature Feedback Form

Architectural drawings or modeling report

This requirement does not apply to floor/ceiling assemblies that separate a relevant room type from a parking garage or non-occupiable space (e.g., a quiet zone that is vertically adjacent to a roof, equipment room or attic). 

This feature is a beta strategy and has an additional documentation requirement (beta feature feedback form). The feedback form supports IWBI in developing new features that are effective and applicable to projects around the world.

WELL Core:

Meet these requirements for the extent of developer buildout.

S07.2 Meet Thresholds for Impact Noise Rating — 1–2 points (max 2)

Applies to: All Spaces.

The following requirements are met:

Verification: Technical Document (Individual), Beta Feature Feedback Form

Testing report that includes the following:

This requirement does not apply to floor/ceiling assemblies that separate a relevant room type from a non-occupiable space (e.g., a quiet zone that is vertically adjacent to a roof, equipment room or attic). 

This feature is a beta strategy and has an additional documentation requirement (beta feature feedback form). The feedback form supports IWBI in developing new features that are effective and applicable to projects around the world.

WELL Core:

Meet these requirements for the extent of developer buildout.

Frequently asked questions

Can an interior project comprised of a single level pursue this feature?

Interiors projects can pursue this feature part as long as there is at least one floor above and/or below the project that includes the room type(s) listed in the feature. 
 
To achieve this feature part, the project must be able to demonstrate that the appropriate floor-ceiling assemblies are used regardless of whether or not your project controls the spaces vertically adjacent to your project. For example, in Part 2, open areas for concentration require the floor-ceiling assembly above to achieve NISR of 42 or higher; if this space is within the project boundary but the space above belongs to a different tenant, the space above would still need to be accessible for testing for Part 2 of this feature. Similarly, if a project has a fitness space within its boundary and there is a different tenant below, access to the space below for testing would be required to assess if that floor-ceiling assembly achieves NISR of 47 or higher. 

References

  1. LoVerde J, Miller E, Nash AP, et al. ICC G2-2010 Guideline for Acoustics. 2010:29.
  2. Joen J, Lee P, Kim P, Yoo S. Subjective evaluation of heavy-weight floor impact sounds in relation to spatial characteristics. J Acoust Soc Am. 2009;125(5):2987-2994.
  3. Ljunggren, Fredrik; Simmons, Christian; Hagberg K. Correlation between sound insulation and occupants’ perception – Proposal of alternative single number rating of impact sound. Appl Acoust. 2014;85:57-68.
  4. Blazier JWE, DuPree RB. Investigation of low-frequency footfall noise in wood-frame, multifamily building construction. J Acoust Soc Am. 1994;96:1521-1532.
  5. Ryu J, Sato H, Kurakata K, Hiramitsu A, Tanaka M, Hirota T. Relation between annoyance and single-number quantities for rating heavy-weight floor impact sound insulation in wooden houses. J Acoust Soc Am. 2011;129(5):3047-3055. doi:10.1121/1.3561660
  6. Structural Building Components Association. Sound Transmission in Wood Floor and Roof Trusses.; 2016.
  7. Rindel J. The relationship between sound insulation and acoustic quality in dwellings. In: Inter-Noise 98. ; 1998.
  8. Understanding IIC & STC Sound Testing.
  9. Warnock ACC. Controlling the Transmission of Impact Sound through Floors. NRC Constr Technol Updat No 25. 1999.
  10. International Code Council. International Building Code.; 2015.