S03 Sound Barriers (WELL v2, Q2 2025)

Concept: Sound · Type: Optimization · Maximum points: 3

Intent

Increase the level of sound isolation and speech privacy between enclosed spaces.

Summary

This WELL feature requires that walls and doors meet a minimum degree of acoustical separation to provide adequate sound isolation and improve speech privacy.

Issue

Sound that transmits from one room to another through walls or doors can be distracting or annoying and also disturb sleep.1–5 There is evidence that links noise annoyance in multi-story housing to poor mental health and perceived stress in residents.6,7 Speech privacy is also reduced when background sound in receiving rooms is lower as part of the room’s intent (e.g., bedroom, restorative space, classroom).1,8 For walls, lightweight construction, glass and demountable partitions are typical in modern design and offer minimum acoustic separation and speech privacy, especially when wall construction is not uniform.9–11

Evidence

Sound transmits through walls directly and around the construction by what is known as flanking. Walls with high sound transmission class ratings (STC) will provide sound isolation, only when the wall is constructed to reduce flanking at points where the wall connects to other building elements. Windows, glass fins or other penetrations diminish performance and should be used sparingly. Doors also reduce performance of walls but can be fitted with gaskets and seals to reduce sound transmission, when the door is closed. Rooms that require high speech privacy can use sound masking systems, in addition to high-performing walls to increase privacy.8

Requirements

S03.1 Design for Sound Isolation at Walls and Doors — 1 point

Applies to: All Spaces.

The following requirements are met:

Verification: Technical Document (Audited)

Architectural drawings

WELL Core:

Meet these requirements for the extent of developer buildout. Demising walls that separate tenant spaces from common spaces or other tenant spaces should use the "Loud zones and other occupiable spaces" category.

S03.2 Achieve Sound Isolation at Walls — 2 points

Applies to: All Spaces.

Meet any one of the following options:

Option 1: Noise isolation class

For walls that separate regularly occupied spaces the following requirements are met:

Verification: Performance Test

Performance verification: Sound Insulation

Test method:

Device requirements:

Loudspeaker:

Reporting and compliance:

Option 2: Speech privacy

For walls that separate regularly occupied spaces the following requirements are met:

Verification: Performance Test

Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.

WELL Core:

Meet these requirements for the extent of developer buildout. Demising walls that separate tenant spaces from common spaces or other tenant spaces should use the "Enclosed Loud zones" and "All other occupiable spaces" threshold.  

References

  1. Hongisto V, Oliva D, Keränen J. Subjective and objective rating of airborne sound insulation - living sounds. Acta Acust united with Acust. 2014;100(5):848-863. doi:10.3813/AAA.918765
  2. Park HK, Bradley JS, Grover BN. Rating Airborne Sound Insulation in Terms of the Annoyance and Loudness of Transmitted Speech and Music Sounds.; 2008.
  3. 3Xie H, Kang J, Mills GH. Clinical review: The impact of noise on patients’ sleep and the effectiveness of noise reduction strategies in intensive care units. Crit Care. 2009;13(2):208. doi:10.1186/cc7154
  4. Strauch C, Brandt S, Edwards-Beckett J. Implementation of a quiet hour: effect on noise levels and infant sleep states. Neonatal Netw. 1993;12(2):31-35.
  5. Parthasarathy S, Tobin MJ. Sleep in the intensive care unit. Instensive Care Med. 2004;30:197-206.
  6. Jensen HAR, Rasmussen B, Ekholm O. Neighbour noise annoyance is associated with various mental and physical health symptoms: results from a nationwide study among individuals living in multi-storey housing. BMC Public Health. 2019;19(1):1508. doi:10.1186/s12889-019-7893-8
  7. Jeon JY, Ryu JK, Lee PJ. A quantification model of overall dissatisfaction with indoor noise environment in residential buildings. Appl Acoust. 2010;71(10):914-921. doi:10.1016/j.apacoust.2010.06.001
  8. Hongisto V, Varjo J, Leppämäki H, Oliva D, Hyönä J. Work performance in private office rooms: The effects of sound insulation and sound masking. Build Environ. 2016;104(1):263-274. doi:10.1016/j.buildenv.2016.04.022
  9. Trevathan JW, Pearse JR. The effect of workmanship on the transmission of airborne sound through light framed walls. Appl Acoust. 2008;69(2):127-131.
  10. Craik RJM, Steel JA. The effect of workmanship on sound transmission through buildings: Part 1 - Airborne sound. Appl Acoust. 1989;27(1):57-63.
  11. Craik RJM. The consequences of lightweight buildings on sound transmission. Build Serv Eng Res Technol. 1998;19(1):B1-B4.