S03 Sound Barriers (WELL v2, Q2 2025)
Concept: Sound · Type: Optimization · Maximum points: 3
Intent
Increase the level of sound isolation and speech privacy between enclosed spaces.
Summary
This WELL feature requires that walls and doors meet a minimum degree of acoustical separation to provide adequate sound isolation and improve speech privacy.
Issue
Sound that transmits from one room to another through walls or doors can be distracting or annoying and also disturb sleep.1–5 There is evidence that links noise annoyance in multi-story housing to poor mental health and perceived stress in residents.6,7 Speech privacy is also reduced when background sound in receiving rooms is lower as part of the room’s intent (e.g., bedroom, restorative space, classroom).1,8 For walls, lightweight construction, glass and demountable partitions are typical in modern design and offer minimum acoustic separation and speech privacy, especially when wall construction is not uniform.9–11
Evidence
Sound transmits through walls directly and around the construction by what is known as flanking. Walls with high sound transmission class ratings (STC) will provide sound isolation, only when the wall is constructed to reduce flanking at points where the wall connects to other building elements. Windows, glass fins or other penetrations diminish performance and should be used sparingly. Doors also reduce performance of walls but can be fitted with gaskets and seals to reduce sound transmission, when the door is closed. Rooms that require high speech privacy can use sound masking systems, in addition to high-performing walls to increase privacy.8Requirements
S03.1 Design for Sound Isolation at Walls and Doors — 1 point
Applies to: All Spaces.
The following requirements are met:
Interior walls meet the following sound transmission class (STC) or weighted sound reduction (Rw) values. If an interior wall meets multiple categories listed, use the highest (i.e., more stringent) STC/Rw value listed.
Interior Wall Type Minimum STC or Rw OR Minimum STC or Rw for
Projects That Achieve Feature S06.1Between loud zones and regularly occupied spaces. 60 OR 60 Between areas for conferencing, learning or sleeping and other regularly occupied spaces. 55 OR 50 Between adjacent quiet zones. 50 OR 45 Between rooms for concentration and other regularly occupied spaces. 45 OR 40 Between circulation zones and regularly occupied spaces. 40 OR 35 Doors that connect two occupiable rooms and doors to mechanical equipment rooms have a non-hollow core, minimum STC/Rw of 30 and seals at the head, jamb and base.
Verification: Technical Document (Audited)
Architectural drawings
WELL Core:
Meet these requirements for the extent of developer buildout. Demising walls that separate tenant spaces from common spaces or other tenant spaces should use the "Loud zones and other occupiable spaces" category.
S03.2 Achieve Sound Isolation at Walls — 2 points
Applies to: All Spaces.
Meet any one of the following options:
Option 1: Noise isolation class
For walls that separate regularly occupied spaces the following requirements are met:
The project meets the following minimum Noise Isolation Class (NIC) or Weighted Difference Level (Dw) for each wall type, as applicable. If an interior wall meets multiple categories listed, use the highest NIC/Dw value listed.
Interior Wall Type Minimum NIC or Dw OR Minimum NIC or Dw for Projects That Achieve Feature S06.1 Between loud zones and regularly occupied spaces. 55 OR N/A Between areas for conferencing, learning or sleep and other regularly occupied spaces. 50 OR 45 Between adjacent quiet zones. 45 OR 40 Between rooms for concentration and other regularly occupied spaces. 40 OR 35 Between circulation zones and regularly occupied spaces. 35 OR 30
Verification: Performance Test
Performance verification: Sound Insulation
Test method:
- Loudspeaker should be placed near the wall at the opposite side of the room from the wall that is being tested. If a non-omnidirectional speaker is used, to the extent possible, it should be aimed into a trihedral corner along this wall (i.e., where two walls join at right angles).
- The minimum level of the operating loudspeaker should be at least 90 dBA.
- Each measurement should last at minimum 30 seconds in each receiving room measurement location. If the receiving room has already been assessed for compliance with Feature S02 Part 1, data from the measurement (L90) may be used for Reporting & Compliance in lieu of taking an additional NIC/Dw measurement in that receiving room.
Device requirements:
Loudspeaker:
- Minimum 0.25 m [10 in] diameter
- Minimum frequency response of at least 100 Hz – 4 kHz
- Maximum output of at least 100 dB
- Noise generator capable of producing white/pink noise of equal sound energy across all frequencies of interest
Reporting and compliance:
- Sound isolation and speech privacy metrics must be reported by following one of the following methods, as applicable:
- Noise Isolation Class (NIC) is calculated from L10 of the source measurement, L90 of the receiving location with source on, and L90 of the ambient background level (source off) of the receiving room (see below). L10 and L90 measurements for NIC calculations are evaluated across 125 Hz and 4 kHz.
- Sound Insulation (Dw) is calculated from Leq of the source measurement and receiving room with source on and off, assuming a room reverberation time of 0.5 seconds (unless known through evaluation of S04.2, as applicable). Both Dw and dBA L90 measurements are evaluated across 100 Hz and 3150 Hz.
- Speech Privacy Potential (SPP) is the sum of either Noise Criteria (NC) + Noise Isolation Class (NIC) OR background noise (dBA L90) + sound insulation (Dw).
- Noise Criteria (NC) is the single number criteria based on L90 background noise measurement from 63 Hz to 8 kHz taken in the receiving room space (see Reporting & Compliance for Internally Generated Noise for additional guidance).
Option 2: Speech privacy
For walls that separate regularly occupied spaces the following requirements are met:
The sum of the measured Noise Isolation Class (NIC) or Weighted Difference Level (Dw) combined with the Noise Criteria Rating (NC) or A-weighted Sound Pressure Level (LAeq) within a room achieves the following minimum values, as applicable. If an interior wall meets multiple categories listed, use the highest value listed.
Source Room
Receiver Room
Minimum NIC + NC or Dw + LAeq
Enclosed loud zones
Open areas for concentration
Circulation zones
80
All other occupiable areas
85
Enclosed areas for conferencing
Enclosed areas for learning
Enclosed areas for sleeping
Open areas for concentration
Circulation zones
75
Enclosed quiet zones
80
Enclosed areas for conferencing
Enclosed areas for learning
Enclosed areas for sleeping
85
Enclosed quiet zones
Open areas for concentration
Circulation zones
70
Enclosed quiet zones
75
Enclosed areas for conferencing
Enclosed areas for learning
Enclosed areas for sleeping
80
Verification: Performance Test
Refer to the Performance Verification Guidebook for information on sensor/testing requirements, required testing duration and compliance calculations.
WELL Core:
Meet these requirements for the extent of developer buildout. Demising walls that separate tenant spaces from common spaces or other tenant spaces should use the "Enclosed Loud zones" and "All other occupiable spaces" threshold.
References
- Hongisto V, Oliva D, Keränen J. Subjective and objective rating of airborne sound insulation - living sounds. Acta Acust united with Acust. 2014;100(5):848-863. doi:10.3813/AAA.918765
- Park HK, Bradley JS, Grover BN. Rating Airborne Sound Insulation in Terms of the Annoyance and Loudness of Transmitted Speech and Music Sounds.; 2008.
- 3Xie H, Kang J, Mills GH. Clinical review: The impact of noise on patients’ sleep and the effectiveness of noise reduction strategies in intensive care units. Crit Care. 2009;13(2):208. doi:10.1186/cc7154
- Strauch C, Brandt S, Edwards-Beckett J. Implementation of a quiet hour: effect on noise levels and infant sleep states. Neonatal Netw. 1993;12(2):31-35.
- Parthasarathy S, Tobin MJ. Sleep in the intensive care unit. Instensive Care Med. 2004;30:197-206.
- Jensen HAR, Rasmussen B, Ekholm O. Neighbour noise annoyance is associated with various mental and physical health symptoms: results from a nationwide study among individuals living in multi-storey housing. BMC Public Health. 2019;19(1):1508. doi:10.1186/s12889-019-7893-8
- Jeon JY, Ryu JK, Lee PJ. A quantification model of overall dissatisfaction with indoor noise environment in residential buildings. Appl Acoust. 2010;71(10):914-921. doi:10.1016/j.apacoust.2010.06.001
- Hongisto V, Varjo J, Leppämäki H, Oliva D, Hyönä J. Work performance in private office rooms: The effects of sound insulation and sound masking. Build Environ. 2016;104(1):263-274. doi:10.1016/j.buildenv.2016.04.022
- Trevathan JW, Pearse JR. The effect of workmanship on the transmission of airborne sound through light framed walls. Appl Acoust. 2008;69(2):127-131.
- Craik RJM, Steel JA. The effect of workmanship on sound transmission through buildings: Part 1 - Airborne sound. Appl Acoust. 1989;27(1):57-63.
- Craik RJM. The consequences of lightweight buildings on sound transmission. Build Serv Eng Res Technol. 1998;19(1):B1-B4.