L09 Occupant Lighting Control (WELL v2, Q2 2025)
Concept: Light · Type: Optimization · Maximum points: 3
Intent
Provide individuals with customizable lighting environments.
Summary
This WELL feature requires projects to implement innovative lighting strategies that take into account personal preferences of users, as well as their interaction with the physical space.
Issue
Humans spend about 90% of their time indoors and the ambience of the indoor environments has an impact on the well-being and productivity of occupants. Lighting in a space has been shown to have a positive impact on mood and cognitive performance.1,2 Lighting environments that are customizable by individuals have been shown to improve satisfaction levels.3 The ages of occupants have an impact on the light levels required for visual acuity.4,5 Lighting guidelines recommend twice the light levels for individuals over the age of 65 years, compared to individuals between the ages of 25 years and 65 years.5,6 As humans age, the transmission of light through their lens is reduced. This is due to age related changes, including increased light absorption by the lenses smaller pupil size, increased scattering of light due to thicker lenses and yellowing of the lenses.7,8
Evidence
Developing a lighting environment that not only seeks to satisfy the visual and circadian requirements of individuals, but also creates a customizable environment helps to improve productivity, mood and well-being. Innovative lighting strategies, including the customization of a user’s immediate environment, can contribute to occupant satisfaction with the space. Creating zones with lighting conditions that are distinct from the lighting in regular workspaces, can create a comfortable and informal environment that individuals can utilize for social interaction. Lighting environments can help to improve mental health, reduce stress and improve visual acuity.1,9
Requirements
L09.1 Enhance Occupant Controllability — 1–2 points (max 2)
Applies to: All Spaces.
Meet all of the following options:
Option 1: Lighting zones
Ambient lighting systems meet the following requirement:
All regularly occupied spaces contain lighting zones as shown in the table below (note: individual rooms smaller than the areas below and/or that have occupancies less than those listed in the table are considered separate zones):
Tier Number of Zones Number of Zones Points 1 One per {{well-unit}}650 ft2|60 m2{{/well-unit}} OR One per 10 occupants {{well-points}} 1|0.5 {{/well-points}}
2 One per {{well-unit}}320 ft2|30 m2{{/well-unit}} OR One per 5 occupants {{well-points}} 2|1{{/well-points}}
Verification: Technical Document (Audited)
Architectural drawings
Option 2: Lighting control system
Each lighting zone meets the following requirements:
Lighting systems have at least three lighting levels or scenes that allow for changes in light levels.
Lighting systems have the ability to change at least one of the following:
- Color.
- Correlated color temperature (CCT).
- Distribution of light by controlling different groups of lights or through preset scenes.
All regular occupants have control over their immediate lighting environment through at least one of the following:
- Manual controls (e.g. switches or control panels) located in the same space as each lighting zone.
- Digital interface available on a computer or phone.
Lighting for presentation or projection walls are separately controlled.
Verification: Professional Narrative
Projects may identify spaces within the project boundary where lighting controls are limited to certain regular occupants (e.g., facilities staff, office manager) provided that these spaces do not make up more than 10% of the project size.
WELL Core:
Meet these requirements in non-leased spaces. To earn an additional point, also meet these requirements in leased spaces.
WELL Core projects where non-leased space represents 40% or more of total project area may pursue the additional point without achieving the feature requirements in tenant spaces. Projects utilizing this pathway should include a note on the documentation required by the feature.
L09.2 Provide Supplemental Lighting — 1 point
Applies to: All Spaces; excluding Dwelling Units, Guest Rooms.
Meet all of the following options:
Option 1: Supplemental lighting availability
The project meets the following requirements:
Supplemental light fixtures (e.g., task lights) are provided upon request to all employees at no cost and requests are fulfilled within eight weeks.
At least one supplemental light fixture is available for trial purposes.
Verification: Policy and/or Operations Schedule
Performance verification: Visual Lighting
Test method:
- The measuring instrument is placed in the center of the flat surface of the working plane with the aperture facing upward.
- Ensure that the shadow of the WELL Performance Testing Agent does not fall on the measuring instrument while the measurements are taken.
Device requirements:
- All illuminance measurements are to be conducted with a cosine corrected illuminance meter.
- Range: 5-50,000 lux
- Maximum acceptable overall error: ±5% (at values up to 2000 lux)
- Resolution: 1 lux (at values up to 2000 lux)
- The illuminance meter is calibrated as per manufacturer specifications in an ISO/IEC 17025:2017 Accredited Calibration Lab, or calibration must be NIST traceable.
Reporting and compliance:
- The average light levels across identical tasks must meet the target illuminance throughout the project boundary.
- The lowest light level measured across workspaces must be at least half of the target illuminance.
Option 2: Supplemental lighting requirements
Supplemental light fixtures meet the following requirements:
Light levels are controllable by occupants, independently from the ambient lighting system.
The location of the light is adjustable by users of the workstation.
Under intended use, the light-emitting element is not visible to users.
Verification: Technical Document (Audited)
Product specification sheet(s)
WELL Core:
Meet these requirements in non-leased spaces. To earn an additional point, also meet these requirements in leased spaces.References
- Küller R, Ballal S, Laike T, Mikellides B, Tonello G. The impact of light and colour on psychological mood: A cross-cultural study of indoor work environments. Ergonomics. 2006;49(14):1496-1507. doi:10.1080/00140130600858142
- Knez I, Kers C. Effects of indoor lighting, gender, and age on mood and cognitive performance. Environ Behav. 2000;32(6):817-831. doi:10.1177/0013916500326005
- Veitch JA, Newsham GR. Exercised control, lighting choices, and energy use: An office simulation experiment. J Environ Psychol. 2000;20(3):219-237. doi:10.1006/jevp.1999.0169
- Illuminating Engineering Society. Recommended Practice for Lighting and the Visual Environment for Seniors and the Low Vision Population. Illuminating Engineering Society https://www.ies.org/store/recommended-practices-and-ansi-standards/lighting-and-the-visual-environment-for-seniors-and-the-low-vision-population/.
- Illuminating Engineering Society. Lighting Handbook. 10th ed. Illuminating Engineering Society; 2011. https://www.ies.org/store/lighting-handbooks/lighting-handbook-10th-edition/.
- Illuminating Engineering Society. Recommended practice for office lighting. 2013. https://www.ies.org/store/recommended-practices-and-ansi-standards/american-national-standard-practice-for-office-lighting/.
- Pokorny J, Smith VC, Lutze M. Aging of the human lens. Appl Opt. 1987;26(8):1437. doi:10.1364/AO.26.001437
- Owsley C. Aging and vision. Vision Res. 2011;51(13):1610-1622. doi:10.1016/j.visres.2010.10.020
- Gifford R. Light, decor, arousal, comfort and communication. J Environ Psychol. 1988;8(3):177-189. doi:10.1016/S0272-4944(88)80008-2