WELL v2, Q2 2025 — this page reflects the WELL v2, Q2 2025 addenda of the WELL Building Standard.

Official source: https://v2.wellcertified.com/en/wellv2/appendix/a1

Appendix A1 — Air (WELL v2, Q2 2025)

eACH = Q / [room volume]18

Where Q = A + B + C + D (total clean volumetric air flow rate)

To determine the total clean volumetric air flow rate (Q) for a room, sum the air flow rates for individual systems (as applicable to the HVAC system) per the calculations below.

A: Ventilation Systems18
The greater of:
  • The full mechanical HVAC outdoor air supply rate
  • The full mechanical HVAC system’s exhaust rate, provided the transfer air is from non-regularly occupied spaces or outdoors
B: CADR-rated Media Filters (Standalone Systems)17,18
One of the following:
  • The full m-CADR rate (AHAM Certified per ANSI/AHAM Standard AC-5) or, if unavailable,
  • The full smoke-CADR rate (AHAM Certified per ANSI/AHAM Standard AC-1)
C: In-duct or non CADR-rated Media Filters18
Multiply the air supply rate (e.g., mechanical HVAC fan, blower fan) by the weighted clean air below:
MERV-A
(ASHRAE 52.2)
ePM2.5
(ISO 16890)
Weighted Clean Air Factor
(MERV E2 [1-3 um] minimum arrestance efficiency)
< 13 < 80% 0%
13 80% 85%
14-15 85% 90%
16 90% 95%
HEPA 99% 99%
D: In-duct UVGI17
Multiply the air supply rate by the infectious aerosol reduction efficiency determined in accordance with ANSI/ASHRAE 185.1 with MS2 challenge organism.